5 Commissioning

38

Power units 02.06

Alternative setting:
Simulate a load failure, and then adjust the “load fail” trimmer so that the yel-
low “load fail” LED just lights up.

5.5.2 Setting for master-slave and free-running economy circuit

5.6 External changeover of operating modes

For this to be possible, an external switch must be wired between Terminal 8
and Terminal 6.

If the switches S12 and S13 are closed, an external changeover to phase-
angle control is not possible.

v Section 6.3 “Summary of possible settings”

5.7 Blown fuse indication

If a short-circuit occurs, the built-in semiconductor fuse switches within half a
supply cycle, to protect the thyristors. When the fuse is blown, the “fuse” LED
lights up,

v Section 8.2 “Replacing the semiconductor fuse”

With extra code TR or TO, an output signal is also available.

v Section 4.1 “Connection diagram”

H

When using master-slave and free-running economy circuits, the
settings must be made in both thyristor power units.

H

The smallest change of resistance that can be detected is 5% of
the nominal load resistance (10% in an economy circuit).

Switch

Operating mode

open

burst-firing mode

closed

phase-angle control

H

The external switch can only be used to change from burst-firing to
phase-angle control when the internal switch S3 is open, since this
switch is in parallel with the external switch S.