7 technical data, 1 load circuit, 2 control – JUMO 709040 TYA-110 thyristor power unit Operating Manual User Manual
Page 51: 3 general data, Technical data, Load circuit, Control, General data

51
7 Technical data
7.1 Load circuit
7.2 Control
7.3 General data
Nominal load voltage
24V-20%/+15% AC 45 — 63Hz
42V-20%/+15% AC 45 — 63Hz
115V-20%/+15% AC 45 — 63Hz
230V-20%/+15% AC 45 — 63Hz
265V-20%/+15% AC 45 — 63Hz
400V-20%/+15% AC 45 — 63Hz
460V-20%/+15% AC 45 — 63Hz
500V-20%/+15% AC 45 — 63Hz
(supply voltage for control electronics = nominal load voltage)
Continuous load
current I
L
25A, 50A, 75A, 100A, 150A, 250A
Load types
resistive and resistive-inductive loads (B
≤ 1.2 Tesla)
Current limiting
With phase-angle control, the load current can be adjusted over the range
10 — 100% I
N
by a trimmer on the front panel.
The limiting is based on the rms value of the load current.
Fusing
super-fast semiconductor fuse
TSE circuit
RC network as standard
Power loss
≈ 1.3V x I
L
(A)
Control accuracy
Supply voltage fluctuations within the tolerance range (-20%/+15%)
are accurately compensated.
Fluctuations
≤ 0.5%.
Control signal
0 (4) — 20mA
R
I
= 50
Ω
0 (2) — 10V
R
I
= 25k
Ω
0 (1) — 5V
R
I
= 12k
Ω
0/10V (0/5V)
R
I
= 12k
Ω
0/20mA
R
I
= 50
Ω
floating contact
or
manual control by an external 5 k
Ω potentiometer
Input signal
attenuation
adjustment range 100 — 20%
Circuit variants
-
single-phase operation
-
star circuit with accessible star point
-
open delta circuit
-
economy circuit using master-slave principle and subsidiary V
2
control
in burst-firing operation
-
free-running economy circuit (star or delta) only with subsidiary P control
in burst-firing operation
Operating modes
-
phase-angle control for resistive and transformer loads, with soft start
(with current limiting for extra codes TR, TO)
-
burst-firing operation for resistive or transformer load
Features
Two single-phase units can be linked to form an economy circuit for burst-firing
operation.
-
free-running economy circuit for resistive loads
-
master-slave economy circuit for resistive and transformer loads
Subsidiary control
types
V
2
control as standard.
With extra code TR or TO: free choice of V
2
, P, I
2
control via internal switches.