9.2. MENU CONTROL – Control parameters
CONTROL: Press enter
to switch to menu level 2
>CONTROL<
(INT /
EXT
)
>SELFTUN<
(ALWAYS / OFF / ONCE)
>DYNINT<
(APER / NORM)
>XP INT<
(0.1 ... 99.9)
>TN INT<
(3 ... 9999)
>TV INT<
(0 ... 999)
or
>CONTROL<
(
INT
/ EXT)
>SELFTUN<
(ALWAYS / OFF / ONCE)
>COSPEED<
(0 ... 5)
>XP EXT<
(0.1 ... 99.9)
>TN EXT<
(3 ... 9999)
> TV EXT
(0 ... 999)
>XPU EXT<
(0.1 ... 99.9)
9.2.1.
CONTROL – internal / external control
Factory setting:
INT
The recirculating cooler is conceived for internal and external
temperature control. Switching is carried out in this submenu.
Depending on what is set, only the respective set of parameters is
indicated.
Possible parameters:
INT
internal temperature control
EXT
external temperature control with external Pt100 sensor
The control type can only be adjusted in the -OFF- condition