beautypg.com

Chapter 3 menus – INFICON SQC-222 Thin Film Deposition Controller User Manual

Page 63

background image

Chapter 3

Menus

3-25

In the I/O Setup Menu, any number of “events” can be mapped to the physical inputs
and relays. Options are set by selecting a relay or input and then turning the control
knob to select the desired event. The following table explains each event:

Inputs

Explanation (low to high transition causes)

Start Process

Start the process at Layer 1.

Abort Process

Abort the process. Can only restart at Layer 1.

Start Layer

Start the active layer.

Stop Layer

Stop the active layer.

Start Next Layer

Start the next layer.

Force Final Thickness

End deposition.

Start Process 1-25

Start the selected process.

Soak Hold

Delay the start of deposition.

Zero Thickness

Reset thickness reading to zero.

Zero Time

Reset time setpoint counter to zero.

Output Pocket Ready

The output’s source indexer is on the desired pocket.

Multi Xtal Ready

A multi-crystal sensor head is on the selected crystal.

None

This input is not assigned.

Relays

Explanation (closes when)

Source 1-4 Shutter

Deposit phase for films set to Output.

Sensor 1-4 Shutter

Shutter Delay and Deposit phases of films set to Sensor.

Sensor 1-4 Fail

Sensor is assigned to this layer, and has failed.

All Crystal Good

All sensors assigned to this layer are OK.

All Crystal Fail

All sensors assigned to this layer have failed.

Process Hold

Process is stopped (waiting for Start Layer).

Deposit Phase

Process is in Deposit phase.

PreCond Phase

Process is in Ramp1, Soak1, Ramp2, or Soak2 phase.

SoakHold Phase

Process is in Soak/Hold phase.

Process Active

Process is running (not stopped).

Manual Mode

Process is in Manual mode (not under PID control).

Max Power

Active output is at maximum power (out of material?).

Process Stopped

Process is stopped (not running).

Time Setpoint

The process has been in Deposit phase the indicated time.

Thickness Setpoint

Thickness setpoint reached. Resets on start of next Layer.

Final Thickness

Final thickness reached. Resets on start of next Layer.

Dual Crystal Shutter

Primary sensor failed, switch to secondary.

Multi Xtal Move 1-4

1 sec. pulse to move a multi-crystal head to next position.

Output Pocket 1-8

Source pocket # (Single Mode) or BCD bit # (Multi mode)

None

This relay is not assigned to any event.