Det-Tronics R8471J Single Channel Gas Controller, OPECL User Manual
Page 9

1.1
95-8572
7
normally open/closed relays
The four relays are individually programmed for either 
normally open or normally closed contacts. This 
is accomplished by placing a jumper plug on the 
appropriate pair of pins. Each relay has a set of three 
pins. For normally open operation, place the plug on 
the NO and center pins. For normally closed operation, 
place it on the NC and center pins. The pin groups are 
identified as follows:
J2 – High Alarm
J3 – Auxiliary Alarm
J4 – Low Alarm
J5 – Fault
The controller is programmed at the factory for normally 
open relay contacts.
latching/non-latching relays
The Low and Auxiliary alarm relays are programmable 
as a group for latching or non-latching operation. The 
High alarm relay is always latching. Latching relay 
operation is programmed using rocker switch 1 at SW1 
(SW1-1). For latching operation, place the switch in the 
closed position. For non-latching operation, place it in 
the open position. This switch is set at the factory for 
non-latching relay operation.
normally energized/De-energized relays
The three alarm relays are programmable as a group for 
normally energized (fail-safe) or normally de-energized 
operation. This is accomplished by setting rocker 
switch 2 at SW1 (SW1-2). For normally energized alarm 
relays, place the switch in the closed position. For 
normally de-energized operation, place it in the open 
position. This switch is set at the factory for normally 
de-energized operation.
The Fault relay is always normally energized, regardless 
of the setting of SW1-2.
4 to 20 ma output
Isolated or non-isolated operation of the 4 to 20 mA 
output is selected using a jumper plug at J1. For 
non-isolated operation, as illustrated in Figure 4, place 
the jumper plug in the INT (internal power source) 
position. Place the plug in the EXT position for an 
isolated circuit, as illustrated in Figure 5. The jumper is 
set at the factory for non-isolated operation.
relay
Selectable
Selectable
*
Selectable
*
normally
normally
latch/
open/closed
energized/
non-latch
De-energized
Low
Y
Y
Y
High
Y
Y
N
1
Auxiliary
Y
Y
Y
Fault
Y
N
2
N
Y = Yes
N = No
1
Latching only
2
Normally Energized
No latching option
*
Relays selectable as a group.
Table 1—Selectable Relay Options