controller ProGraMMInG
Refer to Figure 9 to determine the location of
programming jumpers and switches. Table 1 shows the
selectable options for each relay.

NOTE

All controller jumper plugs must be installed. The
controller outputs will not function properly if a
jumper plug is missing.

A2415

SW1-1

CLOSED = LATCHING

OPEN = NON-LATCHING

SW1-2

CLOSED = NORMALLY ENERGIZED

OPEN = NORMALLY DE-ENERGIZED

J1

INT = NON-ISOLATED

EXT = ISOLATED

HIGH ALARM

AUXILIARY ALARM

LOW ALARM

FAULT

NORMALLY

OPEN/CLOSED

RELAY

CONTACTS

Figure 9—Programming Jumper Plugs and Switches

calIBrate SWItcH

B2056

HolD calIBratIon MaGnet

at oUtSIDe BaSe oF JUnctIon

Box at tHIS locatIon

to actIvate calIBratIon SWItcH

reMote leD

Figure 8—Location of Terminals, Reed Switch and LED within

PIRTB Termination Box