Det-Tronics R8471J Single Channel Gas Controller, OPECL User Manual
Page 15

1.1
95-8572
1
7. Fault leD - Flashes upon detection of a system fault
and is on steady during the power-up time delay.
8. reset Pushbutton - Used for various system
programming and calibration functions as well as 
for resetting the controller.
9. Set Pushbutton - Used for various system
programming and calibration functions.
OUTPUTS
The R8471J Controller is available in a Base version and 
a Premium version. The differences between the two 
models are the output configuration and programming 
options.
Base Model - The base controller is furnished with open
collector transistor outputs (rated 100 milliamperes at 
32 volts dc) for the Low alarm, High alarm, Auxiliary 
alarm, and Fault circuits. The normally de-energized 
alarm outputs are energized when their corresponding 
setpoints are exceeded. The fault output is normally 
energized and becomes de-energized upon detection 
of a system fault.
Premium Model - The premium model is furnished
with a set of four relays in place of the four solid 
state outputs. The relays have SPST contacts rated 5 
amperes at 30 Vdc or 250 vac.
This model also includes a selectable isolated/non-
isolated 4 to 20 mA dc current output for transmitting 
system information to other monitoring devices. The 
linear 4 to 20 mA output corresponds to levels from 
0 to 5 LFL-m. If a system fault is detected, the output 
drops to less than 1.0 mA. The current output can be 
calibrated in the field to ensure maximum accuracy. 
(Refer to the “Calibration” section of this manual for 
details.)
AUTOMATIC DIAgNOSTICS AND
FAULT IDENTIFICATION
The microprocessor based controller features self-
testing circuitry that continuously checks for faulty 
sensor or open sensor wiring, low or high input voltage, 
and other problems that could prevent proper system 
response. When power is applied, the microprocessor 
automatically tests memory. In the Normal operating 
mode, it continuously monitors the input signal from 
the OPECL to ensure proper functioning. In addition, 
a “watchdog” timer is maintained to ensure that the 
program is running correctly. If a fault should occur:
— The Fault LED flashes.
— The digital display identifies the nature of the
fault using an alpha-numeric code. Refer to the 
Troubleshooting section for an interpretation of the 
codes.
— The normally energized Fault output is
de-energized.
— The dc current output drops to less than 1 mA.
NOTE
The fault code will be shown for about 2 seconds 
out of every 5 seconds. The gas concentration at 
the sensor will be displayed during the remaining 
time. If more than one fault should occur, the 
highest priority fault will be displayed. 
An alarm condition will normally over-ride a fault 
condition unless the fault condition occurred first. 
However, faults that affect the actual function of the 
controller (F50, F60, F70, F9X) may impair the ability of 
the controller to maintain an alarm output. 
All faults automatically reset except the F9X faults. After 
the fault condition has been corrected, the fault output 
automatically switches to the normal (energized) state, 
the dc current output returns to normal, and the Fault 
LED turns off. Clearing F9X faults requires removing 
operating power from the controller for approximately 
one second.
CAUTION
The fault detection circuitry does not monitor the 
operation of external response equipment or the 
external wiring to these devices. It is important 
that these devices be checked periodically to 
ensure that they are operational.
