Det-Tronics R8471J Single Channel Gas Controller, OPECL User Manual
Page 17

1.1
95-8572
15
When the signal decreases below the high alarm 
setpoint:
— The high alarm is always latching and unaffected by
the latching/non-latching programming for the low 
and auxiliary alarms. High LED is on steady until 
reset.
In the event of a system fault:
— The normally energized Fault output is de-energized
and the Fault LED is illuminated.
reSet
The Reset mode is entered by pressing the Reset 
button located on the front panel of the controller.
When the Reset button is momentarily depressed:
With no alarms or faults occurring — all LEDs turn off 
and all outputs return to their normal condition (basic 
reset). 
If an alarm or fault condition exists — the basic reset 
will not reset the outputs.
When the Reset button is held for 0.5 second:
If an alarm or fault condition exists — the LEDs turn off 
and the outputs return to their normal condition (forced 
reset). 
NOTE
If an alarm or fault condition exists, the controller 
will return to alarm or fault status when the reset 
button is released.
Remote reset capability is also provided. (Remote reset 
performs a forced reset.)
NOTE
The remote reset performs a reset function only. 
It cannot be used for entering other controller 
operating modes.
otHer oPeratInG MoDeS
Setpoint Display, Setpoint Adjustment, Calibration, 
and 4 to 20 mA Current Output Calibration modes are 
also executed by pressing buttons on the controller 
faceplate. Refer to the appropriate sections of this 
manual for details.