beautypg.com

Det-Tronics R8471J Single Channel Gas Controller, OPECL User Manual

Page 6

background image

1.1

95-8572

4

Terminal 3 –

Chassis ground. Connect the
cable shield to this terminal.

NOTE

If local wiring codes permit and if a ground fault
monitoring system is not being used, the minus
side of the dc power source can be connected
to chassis (earth) ground. Alternatively, a 0.47
microfarad, 100 volt capacitor can be installed
(terminal 5 to ground) for best immunity against
electromagnetic interference.

Terminal 4 –

Connect to the positive (+) side of
the 18 to 32 Vdc power source.

Terminal 5 –

Connect to the negative (–) side
of the dc power source.

Terminal 6 –

Make no connections to this
terminal.

Terminal 7 –

4 to 20 mA dc signal input from
OPECL.

Terminal 8 –

A normally open momentary
closure switch can be connected
between this terminal and the
negative (–) side of the power
source for remote reset.

Terminals 9 and 10 – High Alarm Output.

Terminals 11 and 12 – Auxiliary Alarm Output.

Terminals 13 and 14 – Low Alarm Output.

Terminals 15 and 16 – Fault Output.

Premium controller – The relay outputs (terminals 9 to

16) are programmed for the desired operation using the
procedure described in the “Controller Programming”
section of this manual.

Base controller – Connections to open collector

transistor outputs are made at terminals 10, 12, 14, and
16. Terminals 9, 11, 13, and 15 are not used. See Figure
6 for an example of a typical connection to an open
collector transistor output.

NOTE

External equipment that can generate transients
when switching (such as relays)

must have a

transient suppression device (diode) properly
connected across the coil at the time of installation.
This will safeguard the output transistors of the
controller against possible damage. Figure 6
illustrates an inductive load with a diode used for
transient suppression.

ISOLATED OUTPUT
CURRENT LOOP

CHASSIS GROUND

POWER

SENSOR

EXTERNAL RESET

HIGH ALARM

HIGH ALARM / OC

AUX. ALARM

AUX. ALARM / OC

LOW ALARM

LOW ALARM / OC

FAULT

FAULT / OC

1

3

4

5

6

7

8

9

10

11

12

13

14

15

16

+

+

+

18 TO 32VDC

GROUND

POWER

SIGNAL

HIGH

ALARM

AUXILIARY

ALARM

LOW

ALARM

FAULT

RESET

24

VDC

+

24

VDC

+

2

4-20 MA

A2413

R8471J CONTROLLER

*

*

NO CONNECTION

OC = OPEN COLLECTOR OUTPUT

(BASE MODEL ONLY)

–24 VDC

+24 VDC

– 4-20 MA

1

2

3

4

5

6

7

8

9

10

11

12

13

MODEL OPECL

GAS DETECTOR

+ 4-20 MA

–24 VDC

+24 VDC

2

1

NOTES: 1 INTERNAL JUMPER REQUIRED

FOR NON-ISOLATED CURRENT

OUTPUT (SINGLE POWER

SUPPLY).

2 250 OHM RESISTOR REQUIRED.

Figure 5—A Typical System with Relay Outputs and Isolated Current Output