beautypg.com

Typical system application, Startup procedure, Checkout procedure – Det-Tronics C7051B, C UV Flame Detector User Manual

Page 20

background image

TYPICAL SYSTEM APPLICATION

The following application is an example only. For assis-
tance in adapting a system to your individual require-
ments, contact Application Engineering at Detector
Electronics.

The system illustrated in Figure 19 incorporates two con-
trollers that monitor eight detectors.

STARTUP PROCEDURE

CAUTION

Secure output loads before startup as described
in the “Manual Check in Normal Mode” subsec-
tion of the “Checkout Procedure.”

1. After setting the selection switches and making all

electrical connections, make sure that power is off
and plug controllers into connectors.

2. Turn on power and go through checkout proce-

dures.

3. If the controllers appear to be operating normally,

remove mechanical blocking devices and restore
power to the extinguishing loads.

CHECKOUT PROCEDURE

MANUAL CHECK OF OPTICAL INTEGRITY

1. Place keylock switch in TEST position.

2. FAULT LED turns on.

3. INHIBIT LED turns on.

4. ZONE display indicates the zone selected.

DETECTOR display shows a “0”.

5. STATUS display indicates a “1”. (If any other num-

ber appears, see “Troubleshooting” section.)

6. Push and hold TEST/ACCEPT button. If the lens is

clean, a ZONE OUTPUT LED flashes to indicate the
zone of the detector being tested (after time delay).

7. Appropriate FIRE LOGIC LEDs are turned on if vot-

ing requirements are met.

(Surveillance zones 5-8 are not voted on and will
not turn on FIRE LOGIC LEDs).

8. Release TEST/ACCEPT button, ZONE OUTPUT

LED remains on steady.

9. Push SELECT button. Controller sequences to the

next lower numbered zone.

10. Repeat steps 6 through 10 until all detectors have

been checked.

18

Zone

Status Outputs

S1

S2

S3

S4

1

1

0

0

0

2

0

1

0

0

3

1

1

0

0

4

0

0

1

0

5

1

0

1

0

6

0

1

1

0

7

1

1

1

0

8

0

0

0

1

Table 3—Relationship of ZONE Display to the

Status Outputs

Table 4—Relationship of SYSTEM STATUS Display

to Status Outputs

Front Panel Display

Status Outputs

Outputs

System Status

S5

S6

S7

S8

Fault

Inhibited

0

0

0

0

0

0

1

1

0

1

0

0

0

1

2

0

0

1

0

0

0

3

0

1

1

0

x***

0

4

0

0

0

1

0

0

5

0

1

0

1

0

0

6*

0

0

1

1

1

0

7**

0

1

1

1

1

0

8

0 or 1

0

0

0

0

1

9

1

1

0

0

0

1

Status Outputs

Logic 0 = 100k ohms to ground (0 volts)

S1 – S8, Fault

Logic 1 = Less than 25 ohms to ground

Outputs Inhibited

(0 volts)

Fire Zones only
Surveillance Zones only
1 on Fire Zones, 0 on Surveillance Zones

*

**

***