18

FIRE ALARM PANEL

WITH APOLLO PROTOCOL

POWER

24 VDC

ALARM

LOOP

FIRE RELAY IS NORMALLY OPEN.
FAULT RELAY IS NORMALLY CLOSED AFTER POWER-UP TIME DELAY,
IN A NO FAULT CONDITION.

ANALOG ADDRESSABLE LOOP
(UNPOLARIZED) TO PREVIOUS
AND NEXT XP95A DEVICE

oi TEST

A1845

FIRE

BLK

RED

BLK

RED

GRY

JUMPER

REF

FAULT

oi

1

2

3

4

5

6

7

8

9

10

RED

YEL

GRN

VIO

BLK

WHT

11

12

13

14

15

16

17

18

19

20

+

+

+

+

APOLLO

MODULE

XP95A

U7602E/U7698E

U7602E/U7698E Detector/Apollo Module Style D (Class “A”) Wiring Diagram

1

2

3

4

5

6

7

8

1

2

4

8

16 32 64

ADDRESS

(BINARY CODED)

SWITCH DIAGRAM ABOVE SHOWS AN ADDRESS

OF 0101010 = 42 CLASS "A" WIRING

A1846

ON

WIRING

CLASS

A

B

0

1

SWITCH SETTING: THE ADDRESS NUMBER IS BINARY ENCODED
WITH ROCKER SWITCH NO. 1 BEING THE LEAST SIGNIFICANT BIT.
EACH ROCKER SWITCH HAS A SPECIFIC BINARY VALUE.
THE ADDRESS IS EQUAL TO THE ADDED VALUE OF ALL CLOSED ROCKER SWITCHES
ALL OPEN SWITCHES ARE IGNORED.
SWITCH NO. 8 SELECTS CLASS A OR B WIRING.

NOTES

1. WIRING SHOWN IS STYLE D, CLASS A.

STYLE B, CLASS B NOT SHOWN AND NOT RECOMMENDED.

2. FOLLOW LOCAL ELECTRICAL CODE WHEN INSTALLING EQUIPMENT.

Apollo Module DIP Switch Setting

APPENDIX B

U7602E WITH THE APOLLO MODULE