Det-Tronics U7602E Unitized UV Flame Detector/Controller User Manual

Page 18

background image

16

Atomized Fuel Fires

Distance

Response Time, Sec.

Fuel

Size

Ft. (M)

(Standard Mode, Zero Time Delay)

25 cps

50 cps

Methanol

Flow Rate

25

.04

.06

10 CC per Sec.

(7.5)

Isopropanol

Flow Rate

50

.04

.07

10 CC per Sec.

(15)

Acetone

Flow Rate

50

.04

.08

10 CC per Sec.

(15)

Heptane

Flow Rate

50

.02

.05

10 CC per Sec.

(15)

Standard Mode, High Sensitivity (25 cps), Medium Arc Rejection Mode, Zero Time Delay

On Axis

Off Axis

Fuel

Size

Distance

Response

Distance

Horizontal

Vertical

Ft.

Sec.

Ft.

Response, Sec.

Response, Sec.

(M)

(M)

+45°

–45°

+45°

–45°

Methane

30” Plume

75

1.2

37.5

1.0

1.7

0.7

1.0

(22.5)

(11.2)

Methanol

1 Sq. Ft.

30

2.3

15

1.2

0.9

1.0

2.5

(0.09 Sq. M)

(9)

(4.5)

Gasoline

1 Sq. Ft.

65

0.8

32.5

0.8

0.9

0.6

0.8

(0.09 Sq. M)

(19.5)

(9.7)

Heptane

1 Sq. Ft.

50

1.2

25

1.0

3.3

0.9

0.8

(0.09 Sq. M)

(15)

(7.5)

HIGH SPEED RESPONSE—
12 millisecond response time to a saturating source (UV input).

ANGLE OF VIEW—
–45 to +45 degrees off centerline in vertical and horizontal planes (methane).

UV ARC REJECTION—
Electrical Arcs.

FALSE ALARM IMMUNITY—

• Direct sunlight.

• Reflected sunlight.

• 75 watt Phillips Far Spot incandescent lamp at 3 feet (1 m).

• 100 watt incandescent light bulb (rough service) at 3 feet (1 m).

• 300 watt incandescent light with clear lens at 3 feet (1 m).

• 250 watt infrared heat lamp at 3 feet (1 m).

• Two 34 watt fluorescent light tubes at 3 feet (1 m).