Det-Tronics U7602E Unitized UV Flame Detector/Controller User Manual
Page 18

16
Atomized Fuel Fires
Distance
Response Time, Sec.
Fuel
Size
Ft. (M)
(Standard Mode, Zero Time Delay)
25 cps
50 cps
Methanol
Flow Rate
25
.04
.06
10 CC per Sec.
(7.5)
Isopropanol
Flow Rate
50
.04
.07
10 CC per Sec.
(15)
Acetone
Flow Rate
50
.04
.08
10 CC per Sec.
(15)
Heptane
Flow Rate
50
.02
.05
10 CC per Sec.
(15)
Standard Mode, High Sensitivity (25 cps), Medium Arc Rejection Mode, Zero Time Delay
On Axis
Off Axis
Fuel
Size
Distance
Response
Distance
Horizontal
Vertical
Ft.
Sec.
Ft.
Response, Sec.
Response, Sec.
(M)
(M)
+45°
–45°
+45°
–45°
Methane
30” Plume
75
1.2
37.5
1.0
1.7
0.7
1.0
(22.5)
(11.2)
Methanol
1 Sq. Ft.
30
2.3
15
1.2
0.9
1.0
2.5
(0.09 Sq. M)
(9)
(4.5)
Gasoline
1 Sq. Ft.
65
0.8
32.5
0.8
0.9
0.6
0.8
(0.09 Sq. M)
(19.5)
(9.7)
Heptane
1 Sq. Ft.
50
1.2
25
1.0
3.3
0.9
0.8
(0.09 Sq. M)
(15)
(7.5)
HIGH SPEED RESPONSE—
12 millisecond response time to a saturating source (UV input).
ANGLE OF VIEW—
–45 to +45 degrees off centerline in vertical and horizontal planes (methane).
UV ARC REJECTION—
Electrical Arcs.
FALSE ALARM IMMUNITY—
• Direct sunlight.
• Reflected sunlight.
• 75 watt Phillips Far Spot incandescent lamp at 3 feet (1 m).
• 100 watt incandescent light bulb (rough service) at 3 feet (1 m).
• 300 watt incandescent light with clear lens at 3 feet (1 m).
• 250 watt infrared heat lamp at 3 feet (1 m).
• Two 34 watt fluorescent light tubes at 3 feet (1 m).