Det-Tronics ATX10 Transmitter User Manual
Page 34
2.5
95-8657
32
appenDix D
IECEx APPROvAL DESCRIPTION
IEC Standards:
IEC60079-0: 2011
Electrical apparatus for explosive atmospheres, General Requirements
IEC60079-1: 2007
Electrical apparatus for explosive atmospheres, Flameproof enclosure “d”
IEC60079-11: 2011
Intrinsic Safety explosive atmospheres Equip protection by Intrinsic Safety
IEC60079-31: 2008
Explosive atmospheres Equip. Dust Ignition Protection by enclosure “t”
IEC60529: 2001
Degrees of Protection Provided by Enclosures (IP Code)
IEC Special Conditions for Safe Use (X):
AC100
• The AC100 Acoustic Sensor must always be installed with the detection head pointing down vertically.
• The AC100 Acoustic Sensor must only be installed in areas where there is a low risk of mechanical damage.
• The AC100 is only to be used connected to the ATX10 Acoustic Transmitter or Model STB Sensor Termination Box.
ATX10
• The ATX10 must only be installed in areas where there is a low risk of mechanical damage.
Warning
Always ensure that the detector/junction box hazardous (classified) location ratings are applicable for the
intended use.
Additional Safety Notes:
• The following warning is on the product: Warning: Do not open when an explosive gas atmosphere may be
present. For ambient temperature above 60°C use field wiring suitable for maximum ambient temperature. For
temperature below –10°C use suitable field wiring for the lowest temperature.
• Cable, bushings and the conduit entries shall be of a flameproof type already certified according to relevant IEC
standard, rated IP66, so the protection principle employed will not be impaired.
• Unused conduit entries shall be closed using flameproof stop plugs certified for the conditions of use (IP66
minimum). The stop plugs should be removable only with the aid of a tool.
• Shielded cable is required.
AC100
IECEx ULD13.0002X
Ex d ib IIC T4 Gb
Ex tb IIIC T80°C Db
Tamb: –55°C to +75°C
IP66
ATX10
IECEx ULD13.0003X
Ex d IIC T6 Gb
Ex tb IIIC T80°C Db
Tamb: –55°C to +75°C
IP66