Installation – Det-Tronics ATX10 Transmitter User Manual
Page 13
2.5
95-8657
11
impOrtant saFety nOtes
CaUTiOn
the wiring procedures in this manual are intended
to ensure proper functioning of the device under
normal conditions. However, because of the
many variations in wiring codes and regulations,
total compliance to these ordinances cannot be
guaranteed. Be certain that all wiring complies
with the NeC as well as all local codes. If in doubt,
consult the authority having jurisdiction before
wiring the system. Installation must be done by a
properly trained person.
CaUTiOn
this product has been tested and approved
for use in hazardous areas. However, it must
be properly installed and used only under the
conditions specified within this manual and
the specific approval certificates. Any device
modification, improper installation, or use in a
faulty or incomplete configuration will render
warranty and product certifications invalid.
CaUTiOn
the device contains no user serviceable
components. Service or repair should never be
attempted by the user. Device repair should be
performed only by the manufacturer.
LiabiLiTies
the manufacturer’s warranty for this product is
void, and all liability for proper function of the
detector is irrevocably transferred to the owner or
operator in the event that the device is serviced or
repaired by personnel not employed or authorized
by Detector electronics Corporation, or if the
device is used in a manner not conforming to its
intended use.
CaUTiOn
observe precautions for handling electrostatic
sensitive devices.
CaUTiOn
Unused conduit entries must be closed with
suitably certified flameproof blanking elements
upon installation.
installatiOn
Note
Detector housings must be electrically connected
to earth ground. A dedicated earth ground
terminal is provided.
Note
the AC100 has an Intrinsic Safety (IS) Barrier.
Proper NeC/CeC IS grounding must be ensured.
Note
the detector must always be installed per local
installation codes.
Note
Use of a threaded adapter for connecting the
AC100 to the StB or AtX10 is prohibited.
Note
the AtX10 transmitter module is shipped with the
SD card installed in the memory module. A piece
of tape has been installed to secure the card in
place and prevent it from becoming dislodged
during shipping. See Figure 6. the shipping
tape should be removed prior to commissioning
the acoustic detector.
SENSOR TERMINATION BOX
A Det-Tronics sensor termination box (Model STB)
is required for installations where the AC100 is not
connected directly to the ATX10 transmitter housing.
When installing the AC100 remotely from the transmitter,
shielded cable using twisted pair wires for signal is
required to prevent possible nuisance EMI/RFI. The
maximum cable length between the AC100 and the
ATX10 is 500 ft.
TAPE PROVIDED FOR SHIPPING
PURPOSES ONLY. REMOVE TAPE
PRIOR TO FINAL INSTALLATION.
A2622
Figure 6—Remove Shipping Tape from Transmitter module