beautypg.com

Example 4 - program mode – Despatch Protocol Controller User Manual

Page 43

background image

37

Figure 9. Example Temperature Profile

NOTES: MMSS
(minutes/seconds) and

EF

selected in the tune mode. Event
1 wired properly for autostart,
events 2 - 3 are not used. No
hold at last setpoint.

Soak-Deviation = ±5

EF (also

assured soak limit). Minimum
operating temperature is 70

EF.

Example 4 - Program Mode

Autostart the oven after two hours and follow the characteristic curve below.

Display

Setting(s)

HL

240

PRO-

1

SEG-

1

2

3

4

5

6

RAMP

0001

0100

0030

0100

0100

0030

E-1 *

OFF

ON

ON

ON

ON

ON

E-2

_____

_____

_____

_____

_____

_____

E-3

_____

_____

_____

_____

_____

_____

TEMP

70

130

160

130

220

100

SOAK

0200

0030

0100

0100

0200

0001

E-1

OFF

ON

ON

ON

ON

OFF

E-2

_____

_____

_____

_____

_____

_____

E-3

_____

_____

_____

_____

_____

_____

SOAK-DEV

5

GOTO

End

REPEAT TIMES

1____

HOLD

NO

* Only E1 event is turned on.