WARNING!

TO DRAIN FIELD

SEWER LINE

FUSION CONTROL PANEL

BLOWER

RISER AND LID

FUSION

OPTIONAL SEPTIC TANK INSTALLATION

MAY BE REQUIRED BY LOCAL

OR STATE REGULATIONS

AIR LINE

CLEAN-OUT

Figure 11, Typical Fusion

®

Layout

sk2650

1. The blower must be connected to a grounded, metallic, permanent wiring system, or

an equipment-grounding terminal or lead on the product.

2. Place the blower where it is easily accessible for maintenance and inspection.
3. Install the blower in an area where it will be protected from damage and inundation.

Also make certain the location has good ventilation.

4. Install the blower on a foundation that is level and solid.
5. Excavate trenches for two air lines from blower to the unit.
6. Install two separate 1/2" (13 mm) air lines from the blower to the unit. Length of piping

must be less than 17' (5 m). If distances from 17' (5 m) to 33' (10 m) are required,

use 3/4" (19 mm) diameter piping (Figure 12). If longer air lines are needed, consult

the factory.

7. The blower is provided with two discharge ports. The blower label is color-coded with the

aeration outlet port being BLUE and the backwash outlet port being RED (Figure 12).

8. The air port inlets on the Fusion

®

are also color-coded, BLUE for aeration and RED

for backwash (Figure12).

9. Attach the barbed end of each PVC tee (included in the blower box) to the blower

using the rubber elbows (Figure 12).

10. Attach the small diameter black air tubing (included in the blower box) to barbed fitting

on PVC tee. Black air tubing and blower power cord should be routed to the alarm

panel through conduit. Attach the two black air tubing lines to the two air pressure

sensor barbed fittings in the alarm panel (Figure 12).

11. Connect the remaining end of each PVC tee to the airlines installed in Step 6.

!

RISER CONFIGURATION

DECORATIVE ROCK CONFIGURATION

INTERIOR CONFIGURATION

RUBBER

ELBOWS

POWER

CORD

BLUE AIR

LINE

RED AIR

LINE

CONDUIT TO

PANEL

AIR LINE

TO PANEL

ADAPTER

BLOWER

AIR LINE

TO PANEL

RED AIR

LINE

BLUE AIR

LINE

BLOWER INSTALLATION AND PLACEMENT

Figure 12

TO PREVENT ELECTRICAL SHOCK FROM

BACK-SIPHONING, LOCATE THE PUMP

ABOVE THE WATER LEVEL.

sk2639