Pr el im in a ry pr el im in a ry – Clarus Environmental Fusion Series Treatment Systems 450/600/800 User Manual
Page 16
16
© Copyright 2012. All rights reserved.
PR
EL
IM
IN
A
RY
PR
EL
IM
IN
A
RY
TROUBLESHOOTING
1. Odor
Offensive odors are often the result of insufficient or
inappropriate bacterial growth. Causes may include
a young or unestablished system, insufficient air
introduction, or the addition of detrimental chemicals
or poisons into the system. Ensure the blower and air
delivery systems are functioning. Check with the owner
regarding chemical use and disinfection habits. Check all
risers and lids to ensure an airtight seal.
2. Foam Formation
Foam formation is observed in the following situations:
1. In the early stage of operation when the
aerobic bacteria colony is establishing itself.
2. When an excess amount of air is supplied for aeration.
3. When the difference between ambient
temperature and water temperature is great.
4. When an excessive amount of detergent is
introduced.
In most cases, foam will disappear with proper operation.
When excessive amounts of detergent have been
introduced to the system, remind the owner to use
appropriate amounts of detergent.
3. Cloudy Treated Water
• Check the amount of scum and sludge:
If too much scum or sludge is observed, transfer
them to the first chamber and adjust recirculation flow
rate as well as backwash time, frequency and duration.
(See backwash flow adjustment)
• Check the aeration situation:
If uneven bubble generation is observed, adjust
valve (1). If aeration is weak, flush the aeration
pipe with air or water.
• Check the recirculation flow rate:
If the recirculation flow rate has increased
after the last inspection, the aeration pipe may
be clogged. Flush the aeration pipe with air or
water. If the recirculation flow rate has decreased after
the last inspection, the airlift pump or recirculation
pipe
may be clogged. Clean them with a brush and
running water.
• Check the color of the returning sludge from the
backwash pipe:
If the color is abnormally dark, decrease the
recirculation flow rate accordingly. If the TSS of
the water from Anaerobic to Aeration Chamber is
high, check the sludge accumulation. If the sludge
accumulation reaches the upper limit, pump out the
sludge. If not, backwashing the Anaerobic Chamber by
using a manual backwash tool (Figure 18) may assist.
4. Blower
Blower motor does not run, with power connected:
•
Check the electric supply to the panel, ensuring 120
volt service.
•
Check that all breakers and fuses in the panels are
on and intact.
•
Check the blower's Auto Stop Mechanism
(see
Figure 24).
Little or No Aeration / Backwash Air:
•
Check the blower motor is running.
•
Check the air line piping connectons at the blower.
•
Check the air filter and clean or replace if necessary.
•
Check the diaphragms and replace if necessary.
•
Check the air piping for leaks, clogs, or dislocations and
correct
accordingly.
•
Verify check valves (if installed) in supply lines are
installed correctly.
Blower - manual backwash does not work:
•
Push the manual backwash button several times,
listening closely for a light click within the unit.
•
If the unit clicks, but the air does not switch from
aeration to back wash, consult the factory.