Pr el im in a ry – Clarus Environmental Fusion Series Treatment Systems 450/600/800 User Manual
Page 10
10
© Copyright 2012. All rights reserved.
PR
EL
IM
IN
A
RY
The recirculation flow is designed to be 1.2-1.8 times that
of the average design inflow. Table 4 indicates starting
flow rates for each unit. However, fine adjustments may be
necessary to ensure optimum performance.
Setting the flow rate:
• Adjust the flow using rates in Table 4.
• The flow rate is adjusted by rotating the gray recirculation
valve (2) and observing the flow at the pipe end.
• There are prescribed lines at the outlet of the recirculation
pipe to aid in approximating the correct flow.
Measuring the flow rate:
• The actual flow rates must be measured to verify flow
after adjustment of the valve and observation at the
pipe end.
• Measure the time in seconds required to fill a 1L
container.
• Compare the time to value ranges in Table 4.
• If necessary, adjust the valve again and collect another
sample to verify the correct flow rates.
In order to prevent plugging of the media in the Aeration
Chamber, the backwash cycle activates at a preset
schedule. If there is no backwash cycle or too short
of a backwash cycle, the unit’s performance will be
adversely affected. Likewise, if the backwash cycle is
too long, performance will be compromised.
The backwash cycle begins at 2:00 AM and lasts for five
minutes. One hour later, another five minute backwash
cycle occurs. Even with these default settings, the waste
water inflow could be too low or too high to optimize
the performance and therefore, must be checked during
each inspection. The backwash initiation time can be
set for any time during a
24-hour period to accomodate unusual water use
patterns. The goal is to set the time when there is no
flow into the unit.
The backwash cycle and sludge transfer from the
Aeration Chamber takes place at the same time.
Verify that the air flow is uniform across the Aeration
Chamber between the two sides during a backwash
cycle. If not, adjust the red backwash valve (3)
accordingly.
Setting the flow rate:
• Switch to a manual backwash cycle by pressing
the pink "Manual Backwash" button on the blower
control pad.
• Set the backwash flow rate by adjusting the gray
sludge transfer valve (4). Use Table 5 to determine
the setting for each Fusion® model.
Measuring the flow rate:
• Measure the actual backwash flow rate at the
outlet of the sludge return pipe in the first chamber
the same way the recirculation flow rate is measured.
• Adjust the gray sludge transfer valve (4) if
necessary to obtain the proper flow.
• Return the blower to normal aeration mode by
pressing the pink button on the blower's control pad.
It is important not to set the flow rate too high
because it can cause excessive agitation within the first chamber
(Sedimentation Chamber). This could result in poor performance.
RECIRCULATION FLOW ADJUSTMENT
BACKWASH FLOW ADJUSTMENT
Table 5 - Backwash Flow Rate Setting
Model
Frequency
ZF450
ZF600
ZF800
Backwash flow rate
(sec/liter)
Twice/day
7-10
5-7
4-6
Valve open (%)
Twice/day
50-55
40-45
40-45
Figure 15 - Flow
Controlling Valve
Figure 14 - Flow
Measurement
Model
ZF450
ZF600
ZF800
Recirculating flow rate
(sec/liter)
29-45
21-32
14-22
Suggested Valve Opening
35-40%
30-35% 30-35%
Table 4 - Recirculation Flow Rates
DOTTED
SCALE
VALVES
SUGGESTED
RANGE
MARKER
CONTAINER
RECIRCULATION OR
BACKWASH PIPE