Step 1: Remove the scum.

Step 2: Remove the sludge

on the filter media.

Step 3: Remove the sludge under the media while washing the filter with tap water.

1)

Anaerobic filter tank

Vacuum

Tap water

2)

3)

: Remove the scum first. If you remove the sludge first, the

water level will decrease and the anaerobic filter will be blocked by the scum.

Figure 22 - Anaerobic Chamber Pumping

Wastewater entering the Fusion

®

contains organic and inorganic materials. If organic in nature, it is treated and decomposed by

microorganisms during the treatment process. If inorganic in nature, it will be stored within the Fusion

®

. The stored materials

accumulate as scum (floating) or sludge (solids on the bottom) and must be removed periodically to ensure the performance of

the Fusion

®

. Please review the Operation and Maintenance sections part B and C to determine when the maximum depths of

scum and sludge have been reached and pumping is required. Follow the procedures in Figures 21 and 22 to remove scum and

sludge from the sedimentation and anaerobic chambers only. When finished, refill both chambers with clean water to prevent the

possibility of flotation.

FUSION

®

PUMPING

Figure 21 - Sedimentation Chamber Pumping

Step 1: Remove the scum.

Step 2: Remove the sludge

1)

2)

Sedimentation-separation tank

Vacuum

ALARM PANEL & BLOWER INSPECTION AND MAINTENANCE

1.

Listen for loud rattling sounds. The blower should hum

softly. If a rattle is heard, ensure that all four legs

securely contact the ground or base medium.

2.

Inspect the filter once the power has been disconnected

by removing the filter retention screw. Then, remove

the cover by snapping the filter cover off the top of the

blower. Clean the filter by knocking the dust out or by

rinsing with water to remove accumulated particles. Be

sure the filter is dry before reinstalling.

3.

Ensure the correct time is shown on the blower's display

screen, keeping in mind that the display shows a

24-hour clock (not AM/PM).

4.

Press the Manual Backwash button and ensure the unit

switches into backwash mode by observing the change

in water flow in the Fusion

®

tank from the recirculation

return line to the sludge transfer line. Be sure to switch

the system back to recirculation by pressing the Manual

Backwash button again.

Inspect the alarm panel for signs of water or odors inside.

Toggle the test switch on the side of the box to check that both

the alarm horn and the alarm beacon light are operational.
Inspect the blower for proper operation. If the blower is not

functioning, refer to the troubleshooting section near the end of

this guide.