Pr el im in a ry, Aeration chamber cleaning – Clarus Environmental Fusion Series Treatment Systems 450/600/800 User Manual
Page 14
14
© Copyright 2012. All rights reserved.
PR
EL
IM
IN
A
RY
AERATION CHAMBER CLEANING
1. Aeration
The aeration system must be flushed every maintenance
visit. There are two flushing methods: (A) Air flushing
and (B) Water flushing. Air flushing must be done every
maintenance visit. Water flushing may be done if there is
a sign of clogging in the Aeration Chamber (e.g. abnormal
increase in recirculation flow).
(A) Air flushing procedure:
• Make sure the blower is in the aeration mode.
• Close gray recirculation valve (2) all the way. (0%)
• Rotate blue aeration valve (1) back and forth from the
0% to the 100% position several times to flush.
• Set valves (1) and (2) back to the appropriate positions.
(See Recirculation Flow Adjustment, pg. 10)
(B) Water flushing procedure: (See Figure 18)
• Make sure the blower is off.
• Close valve (2) all the way.
• Connect a water line to the aeration line as shown in
Fig. 18.
• Gradually open the water faucet and introduce water
into the system.
• Rotate valve (1) back and forth from the 0% to the
100% position several times to flush.
• Turn off the water, remove the water line, and
reconnect the airline to the blower.
• Set valves (1) and (2) back to the appropriate
positions. (See Recirculation Flow Adjustment, pg. 10)
(C) Cleaning the recirculation line:
• Make sure the blower is in the aeration mode. If not,
change the mode by pressing the Manual Backwash
button.
• Open the gray recirculation valve (2) to 100%.
• Flush water through the recirculation line for several
seconds.
• Turn off the recirculation by rotating the gray valve
(2) to 0%.
• Make sure the blower is off. Allow the system to
relax for a few seconds.
• Repeat this cleaning method three times. • A hose or
brush can also be used to clean the recirculation line.
See Figure 20.
• Reset the gray valve (2) to its original position.
2. Backwash
The backwash system must be flushed every maintenance
There are two flushing methods: (A) Air flushing and
(B) Water flushing. Air flushing must be done every
maintenance visit. Water flushing must be done if there
is a sign of clogging in the Aeration Chamber (e.g.
abnormal increase in recirculation flow).
(A) Air flushing procedure:
• Make sure the blower is in the
backwash mode.
• Close the gray sludge transfer
valve (4) all the way.
• Rotate the red backwash valve
(3) back and forth from the 0%
to the 100% position several
times to flush.
• Set valves (3) and (4) back to
FAUCET
BACKFLOW
PREVENTER
WATER
HOSE
CLAMP
TO TREATMENT UNIT
BLOWER
EXISTING
AIR LINE
.
Figure 18
the appropriate positions.
(See Backwash System) (B) Water flushing procedure:
(See Fig. 19)
• Make sure the blower is off.
• Close valve (4) all the way.
• Connect a water line to the backwash airline as shown in
Figure 16.
• Gradually open the water faucet and introduce water into
the system.
• Rotate valve (3) back and forth from the 0% to the 100%
position several times to flush.
• Turn off the water, remove the water line, and reconnect
the airline to the blower.
• Set valves (3) and (4) back to the appropriate positions.
(See Backwash System)
(C) Cleaning the sludge transfer line:
• Make sure that the blower is in the backwash mode. If
not change the mode by pressing Manual Backwash.
• Open the gray sludge transfer valve (4) to 100%.
• Flush water through the sludge transfer line for a few
seconds.
• Repeat this cleaning method three times.
• A hose or brush can also be used to clean the sludge
transfer line. See Figure 20.
• Reset the gray valve (4) to its original position.
• Return the blower to the normal aeration mode. by
pressing Manual Backwash.
3. Foam formation
Make sure there is not an excess amount of foam on the
surface. If excessive foam is present it may indicate high
detergent usage. Meet with owners to inform and educate
them concerning excessive use.
4. Abnormal water level
If the water level exceeds the partition wall, clean the
plastic cage first with a brush, then check for possible
clogging in the filter media section. Clogs may be cleared
by using a manual backwash tool. The manual backwash
tool may also be used to eliminate a clog in the anaerobic
chamber media as well.
Figure 19
BRUSH
Figure 20