2 output config menu, 2 output config menu -3 – CiDRA GVF-100 Gas Volume Fraction Monitoring System User Manual
Page 77

Copyright © 2006 CiDRA Corporation
Page 10-3
20639-01 Rev 03
•
Altitude
Used to calculate the atmospheric pressure corrected for elevation. 
Enter the elevation above or below sea level. 
The following equation is used within the transmitter to correct for 
elevation. 
P
atm
= 14.696 * [1 – ((Alt * 10
-3
)/145.45)]
5.2561
where: P
atm
= absolute atmospheric pressure corrected for altitude (psi)
Alt = altitude (feet)
Note: If an “absolute” scaled pressure transducer is used it is not 
necessary to enter altitude. 
•
Set Date/Time
The date and time is entered in the transmitter in order to set the time 
stamp that will be applied to data downloaded on the USB Port 
(discussed later in this manual). Whenever possible, the time and 
date should to be synchronized to the process control system. Note: 
The time is not automatically updated to reflect daylight savings time. 
10.1.2
Output Config Menu
These inputs are used to configure the various outputs from the 
transmitter. 
•
4-20mA (CH 1 & CH 2)
Several selections are available for outputting under the ‘4-20mA’ 
setup menu screens. 
The ‘Output Sel’ sub-menu selection permits selection of the 
parameter to output on the 4-20mA channels. The GVF meter permits 
selection of the ‘GVF’, ‘SOS’ or ‘Blank’ for no display as the output 
parameter. 
The ‘Power Sel’ selection is used to specify whether ‘Internal’ power 
or ‘External’ power is used to drive the 4-20mA current output. 
The ‘Low End’ and ‘High End’ menu selections allow the user to 
change the upper and lower values that are output on the 4-20mA 
channel based on 5,000 ft/sec as the maximum output value. 
The following figure gives an example screen shot of a user specified 
‘Low End’ setting for 4-20mA CH1. The user settable percentage is 
located on the left side of the bottom line of the display, with the 
corresponding sound speed value shown on the right. The 
percentage represents a point within the output range of the meter. 
This is represented by 0%=0 ft/s and 100%=5000 ft/s. As the 
percentage is changed between 0 -100%, the corresponding sound 
speed value is indicated. 
