MPX Series Magnetostrictive Level Sensors

Rev. B, 4/13

16

Automation Products Group, Inc.

APG...Providing tailored solutions for measurement applications

Tel: 1/888/525-7300 • Fax: 1/435/753-7490 • www.apgsensors.com • [email protected]

Modbus Register Lists

Input Registers (0x04):

Register

Returned Data

30300

Raw Top Float Reading (in mm, unsigned)

30301

Raw Bottom Float Reading (in mm, unsigned)

30302

Temperature Reading (in

0

C, signed)

30303-30304

Calculated Top Float Reading (in selected Units)

30305-30306

Calculated Bottom Float Reading (in selected Units)

NOTE: the Calculated Readings will be returned without a decimal place. In
order to attain the true result, the Decimal Place setting must be taken into
account. Refer to the Decimal Place setting on page 19 for more information.

Holding Registers (0x03):

Register

Function

Value Range

40400

Device Address

1 to 255

40401

Units

1 to 3

40402

Application Type

0-10

40403

Volume Units

0 to 6

40404

Decimal Place

0 to 10364 mm

40405

Max Distance

0 to 10364 mm

40406

Full Distance

0 to 10364 mm

40407

Empty Distance

0 to 10364 mm

40408

Sensitivity

0 to 100

40409

Pulses

0 to 20

40410

Blanking

0 to 10364 mm

40411

Reserved

n/a

40412

Averaging

0 to 100

40413

Filter Window

0 to 10364 mm

40414

Out of Range Samples

0 to 255