7. Troubleshooting



7.1. Evaluation

table

Condition

Visual

Evaluate

Bottom two LEDs rows

alternate flashing.

Signal voltage too low

(less than 0.4 V).

Check sensor wiring. Ensure +5V at pin A, ground at pin B and at least 0.4V at
pin C (Signal).

Use password LLRR LLRR to view sensor voltage on display.

Top two LED rows

alternate flashing.

Signal voltage too high

(greater than 4.8V).

Check sensor wiring. Ensure +5V at pin A, ground at pin B and no more than 4.8V

at pin C (Signal).

Use password LLRR LLRR to view sensor voltage on display.

Middle two LED rows

alternate flashing.

Memory error.

Perform self test RLLR LLRR. If it shows “MEM-FAIL” replace display, otherwise

recalibrate or reset as REMOTE.

Outer two LED rows

alternate flashing.

Invalid calibration.

Try to recalibrate. If condition remains, check if the sensor signal voltage (pin C)

changes as tank level increases. If it doesn’t, replace sensor. If it does, verify
depth of tank. It may be impossible to calibrate a tank with a depth of less than 6

inches.

Bottom four and Upper

four LEDs rows alternate

flashing.

Not receiving data.

The display is configured as a REMOTE. Recalibrate if a MASTER is required. If
the display is supposed to be a REMOTE check communication data lines for

continuity.

No LEDS on.

Check power (Pin 1) and ground (Pin 12) connection.

Master Tank level unit

does not change when

actual tank level is

changing.

No picture

Check sensor wiring. Ensure sensor signal voltage (Pin C) is varying. If it does,

check for same signal changes at Pin 6 of tank level connector (if it is not the

same - repair wiring). If signal is good at both locations try re-calibrating.

Remote Tank level unit

does not follow Master

display.

No picture

Perform self test. If self test is good, verify communication data lines for
continuity. Insure 1-wire data line is not routed near noisy power or RF sources.