Operation manual – Class1 118253 - ITL40 108404-XX - Full User Manual

Page 12

background image

FORM-ENG-0018 REV A 05-27-03

PAGE

11 of 25

S U I T A B L E F O R E X T E R N A L D I S T R I B U T I O N

OPERATION MANUAL

DATE

9/24/2008

PRODUCT GROUP

ITL40

P/N

118404-XX

REV

1.00

607 NW 27th Ave

Ocala, FL 34475

Ph: 352-629-5020 or 1-800-533-3569

Fax : 352-629-2902 or 1-800-520-3473

PRODUCT

Intelli-Tank Level 40

BY

AMS

MANUAL

P/N:118253

P

RINTED

:

1/8/09

Communication method

“1-WIRE”

Using 1-wire communication method.

“CAN”

Using CAN communication method.

CAN device address (if communication method = CAN)

“ADDR=1”

The unit ‘s CAN address is 1 (0xCB).

“ADDR=2”

The unit ‘s CAN address is 2 (0xCC).

“ADDR=3”

The unit ‘s CAN address is 3 (0xCD).

“ADDR=4”

The unit ‘s CAN address is 4 (0xCE).

“ADDR=PCM”

The unit ‘s CAN address is Pump Control Module (0xCA).

Error indications

“NO ERRORS”

No errors detected.

“MEM-ERROR”

Memory error detected.

“CAL-ERROR”

Validation of calibration problem detected.

“NO-COMM”

Not receiving communication from MASTER display.

“SIG-HIGH”

Sensor signal voltage too high (greater than 4.8V).

“SIG-LOW”

Sensor signal voltage too low (less than 0.4V).

“CAL NOT FINISHED” Calibration was started but not completed.
“TYPE-BAD”

Unit type cannot be determined (not MASTER, REMOTE, or CAL INCOMPLETE).

3.7. Configure the communication method

A MASTER display can communicate to other displays that are configured as remotes via CAN or 1-wire.
The 1-wire communication method is the default method and will work with ITL40 and ITL displays.
The CAN communication method is new for the ITL40 displays and is a more robust communication method. This
method requires two wires (CAN high, CAN low) and approved J1939 CAN wiring and connectors. There should be
two (2) 120 ohm terminating resistors located at the ends of the CAN bus (see section 6.3.5).

3.7.1.

Configuring a display as a Master with 1-wire communications

Enter the password LRLL LLLR to set the communication method to 1-wire. If the display was not previously a
MASTER display, calibrate the display

(see section 3.3).


3.7.2.

Configuring a display as a Remote with 1-wire communications

Enter the password LRLL LLLR to set the communication method to 1-wire. If the display is a MASTER display,
enter the password LRLR LRLR to turn the display into a REMOTE.


3.7.3.

Configuring a display as a Master with CAN communications

Enter the password LRLL LLRL to set the communication method to CAN. If the display was not previously a
MASTER display, calibrate the display

(see section 3.3).

Choose the CAN identification address to use (either address 1, 2, 3, 4, or PCM) and enter the appropriate
password to set the address (LRRR LLLL address 1, LRRR LLLR address 2, LRRR LRRR address 3,
LRRR RLLR

address 4, LRRR LRLR address PCM). All REMOTE displays that are to mimic this Master display

must have their addresses matching the MASTER’s.


3.7.4.

Configuring a display as a Remote with CAN communications

Choose the CAN identification address to use (either address 1, 2, 3, 4, or PCM) and enter the appropriate
password to set the address (LRRR LLRL address 1, LRRR LLRR address 2, LRRR LRRL address 3,