FORM-ENG-0018 REV A 05-27-03

607 NW 27th Ave

Ocala, FL 34475

Ph: 352-629-5020 or 1-800-533-3569

Fax : 352-629-2902 or 1-800-520-3473

TECHNICAL DATA SHEET

PAGE

24

OF 26

DATE

3/28/2012

PRODUCT GROUP

THROTTLE CONTROL

P/N

117155

REV

1.23

PRODUCT

TOTAL PRESSURE GOVERNOR (TPG)

BY

AMS


Manual P/N 117684

7. Configuration


7.1. Configure the unit of measure

The TPG can be configured for English (PSI, ºF) of Metric (kPa or bar, ºC) units of measure.

Follow the sequence below to set the TPG’s unit of measure.

+

Display shows MENU 04 SECS and begins counting down. Continue holding IDLE and
MENU until the display shows *SETUP MENU* (4 seconds).

ONCE

The display shows the menu item: UNITS: XXX/ºX.

ONCE

Press the INC switch to select the desired unit of measure: PSI/ºF, kPa/ºC, or bar/ ºC.

ONCE

Press the PRESET switch once. The display shows ---STORED---. The unit of
measure has been saved.

ONCE

Press the IDLE switch once. The display shows —EXITMENU— and then restarts
normal operation.

7.2. Select pressure transducer range (300 PSI, 600 PSI)

Normally the default 300 PSI transducer is sufficient for most pump applications but if a higher pump pressure range
is required the TPG can be programmed to use a 600 PSI transducer.

Follow the sequence below to select the desired pressure transducer range.

+

or

Enter menu level 3 by pressing and holding the IDLE switch while entering
the following password.

INC, DEC, DEC, INC, DEC, DEC, INC, INC

Toggle the MENU/SILENCE switch until the display shows XDCR= XXX.

(XXX = 300 or 600)

Press the INC switch to select the desired pressure transducer range (300 or 600).

ONCE

Press the PRESET switch once. The display shows --- STORED---. The pressure
transducer range has been saved.

ONCE

Press the IDLE switch once. The display shows —EXITMENU— and then restarts
normal operation.