Units (unit of measure configuration), Preset rpm (throttle preset configuration), Hi-idle (high idle configuration) – Class1 117155 - TPG Governor - 117684 EXTERNAL User Manual
Page 17: Preset psi (pressure preset configuration), Bright (display brightness), Display test, Alert tone (configure alert tones), On 5.2.1), On 5.2.5), On 5.2.4)
FORM-ENG-0018 REV A 05-27-03
607 NW 27th Ave
Ocala, FL 34475
Ph: 352-629-5020 or 1-800-533-3569
Fax : 352-629-2902 or 1-800-520-3473
TECHNICAL DATA SHEET
PAGE
16
OF 26
DATE
3/28/2012
PRODUCT GROUP
THROTTLE CONTROL
P/N
117155
REV
1.23
PRODUCT
TOTAL PRESSURE GOVERNOR (TPG)
BY
AMS
Manual P/N 117684
5.2.1.
UNITS (unit of measure configuration)
This menu item allows configuration of the display units of measure.
Use the INC and DEC keys to select the desired units of measure. The options include
PSI/
°
F, kPa/
°
C, bar/
°
C.
Range = PSI / ºF, kPa / ºC, bar / ºC
[default = PSI / ºF]
5.2.2.
PRESET RPM (throttle preset configuration)
This menu item allows configuration of the throttle mode preset.
The display will show PSETrpm XXXX. Use the INC and DEC switches to adjust the RPM value desired for the
throttle mode preset.
Range = 900 RPM to 1400 RPM (in 25 RPM steps).
[default = 1000 RPM]
5.2.3.
HI-IDLE (high idle configuration)
This menu item allows configuration of the high idle (fast idle) setpoint.
The display will show Hi-Idle= XXX. Use the INC and DEC switches to adjust the RPM value desired for the high
idle setpoint.
Range = 900 RPM to 1400 RPM (in 25 RPM steps).
[default = 1100 RPM]
5.2.4.
PRESET PSI (pressure preset configuration)
This menu item allows configuration of the pressure mode preset.
The display will show PSETpsi XXX. Use the INC and DEC switches to adjust the PSI value desired for the
pressure mode preset.
Range = 90 PSI to 130 PSI (in 10 PSI steps)
[default = 100 PSI]
5.2.5.
BRIGHT (display brightness)
This menu item allows configuration the display’s brightness level.
The display will show BRIGHTNESS=X. Use the INC and DEC switches to adjust the value desired display
brightness.
Range = 1 to 15 (1 is dimmest setting)
[default = 15]
5.2.6.
DISPLAY TEST
This menu item allows testing of all of the pixels of the main display and all of the LEDs.
The display will show DISPLAY TEST. Use the INC or DEC switch to turn on all of the LEDs and pixels in the
display.
5.2.7.
ROUND PSI (configure rounding of the pressure value)
This menu item allows enabling/disabling of the “round to nearest 5” of the pressure value.
The display will show ROUND PSI: X. Use the INC and DEC switches to select Y (yes) or N (no).
Round PSI = Y (round to nearest 5) or N (don’t round).
[default = N]
5.2.8.
ALERT TONE (configure alert tones)
This menu item allows enabling/disabling of the alert tones. The alert tones are sounded through the external
alarm output (pin 3 of the 6-pin connector).
The display will show ALERT TONE:X. Use the INC and DEC switches to select Y (yes, enabled) or N (no,
disabled).
Range = Y (Alert tones ON) or N (Alert tones OFF).
[default = Y]