d. Excessive airflow or draft causing flame to leave

burner head.

e. Excessive back pressure causing flame to be

erratic.

3. Control locks out after Trial For Ignition (TFI).

a. No oil to burner.
b. Shorted electrodes.
c. Nozzle clogged.
d. Airflow too high.
e. Ignitor module defective.
f. CAD cell defective.
g. Oil valve stuck open or closed.

Note: The Safety Monitoring Circuit (SMC) is

designed to provide lockout in the event of a

stuck or welded motor relay.

NOTICE

If flame is not established within 15 seconds

of oil valve actuation (known as Trial For

Ignition [TFI]) lockout will occur. Lockout is

indicated by a red LED solid-on located on the

oil primary control.
Latch-up will occur if the control locks-out

three (3) times during a call for heat. This

is indicated by steady-on red and amber

LED's.

Not Applicable to Riello 40 Series Burner, refer to Models F3 and F5 Installation Manual, Riello 40 Series Residential Oil

Burners (C6501010).