SECTION IV: TANkLESS & INDIRECT wATER HEATER PIPING

A. CONNECT TANkLESS HEATER PIPING as

shown in Figure 13. See Table 4 for Tankless Heater

Rating.

WARNING

Install automatic mixing valve at tankless heater

outlet to avoid risk of burns or scalding due to

excessively hot water at fixtures. Adjust and

maintain the mixing valve in accordance with

the manufacturer's instructions. Do not operate

tankless heater without mixing valve.

THE FOLLOWING GUIDELINES SHOULD BE

FOLLOWED WHEN PIPING THE TANKLESS

HEATER:

1. FLOW REGULATION — If flow through the

heater is greater than its rating, the supply of

adequate hot water may not be able to keep up

with the demand. For this reason a flow regulator

matching the heater rating should be installed in

the cold water line to the heater. The flow regulator

should preferably be located below the inlet to the

heater and a minimum of 3’ away from the inlet

so that the regulator is not subjected to excess

temperatures that may occur during “off” periods

when it is possible for heat to be conducted back

through the supply line. The flow regulator also

limits the flow of supply water regardless of inlet

pressure variations in the range of 20 to 125 psi.

2. TEMPERING OF HOT WATER — Installation

of an automatic mixing valve will lengthen the

delivery of the available hot water by mixing some

cold water with the hot. This prevents the possibility

of scalding hot water at the fixtures. In addition,

savings of hot water will be achieved since the user

will not waste as much hot water while seeking a

water temperature. Higher temperature hot water

required by dishwashers and automatic washers is

possible by piping the hot water from the heater

prior to entering the mixing valve. The mixing valve

should be “trapped” by installing it below the cold

water inlet to heater to prevent lime formation in the

valve. Refer to Figure 13.

3. FLUSHING OF HEATER — All water contains

some sediment which settles on the inside of the

coil. Consequently, the heater should be periodically

back washed. This is accomplished by installing

hose bibs as illustrated and allowing water at city

pressure to run into hose bib A, through the heater,

and out hose bib B until the discharge is clear. The

tees in which the hose bibs are located should be

the same size as heater connections to minimize

pressure drop.

4. HARD WATER — A water analysis is necessary

to determine the hardness of your potable

water. This is applicable to some city water and

particularly to well water. An appropriate water

softener should be installed based on the analysis

and dealer’s recommendation. This is not only

beneficial to the tankless heater but to piping and

fixtures plus the many other benefits derived from

soft water.

NOTICE

During summertime operation, the normal

water line on a steam boiler can be raised

1", from 8-/8" to 9-/8" (see Figure 1) for

improved tankless heater performance on

steam boilers.
Use street elbow fittings in tankless in and out

connections to assure adequate clearance of

piping.

CAUTION

Use of hard water with a tankless coil will, over a short period of time, reduce the output of the coil and reduce

the useful life of the coil.