beautypg.com

Warning, Danger – Burnham MEGASTEAM MST288 User Manual

Page 29

background image

9

A. CHIMNEY VENTING

1. Chimney venting is an important part of a safe

and efficient oil fired appliance system. Contact

your local fire and building officials on specific

requirements for restrictions and the installation

of fuel oil burning equipment. In addition,

consult with a professional knowledgeable on

the requirements of NFPA 31 – Standard for the

Installation of Oil-Burning Equipment and NFPA

211 - Standard for Chimneys, Fireplaces, Vents, and

Solid Fuel-Burning Appliances for installations in

the United States

2. The safe venting of oil fired boilers is dependent on

many factors. Some of these factors include:
a. sufficient draft during the entire heating season

to allow for the safe discharge of combustion by-

products and;

b. suitable corrosion protection in the event of

condensing flue gases. Only a trained and

qualified contractor may install this product.

3. The MegaSteam™ can be vented into a fireclay

tile-lined masonry chimney that meets requirements

outlined in Paragraph 4 below. It can also be vented

into a chimney constructed from type L vent or a

factory built chimney that complies with the type

HT requirements of UL 103. The chimney and

vent pipe shall have a sufficient draft at all times,

to assure safe proper operation of the boiler. See

Figure 15 for recommended installation.

WARNING

Do not de-rate the appliance. Failure to fire the

unit at it's designed input may cause excessive

condensation upon the interior walls of the

chimney. In addition, the lower input may not

create enough draft to adequately evacuate the

by-products of combustion.

4. Chimney Inspection – Prior to the installation of

any new or replacement fuel burning equipment the

chimney shall be inspected by a qualified installer.

The chimney shall be inspected for integrity as

well as for proper draft and condensate control.

Some jurisdictions require the use of a liner when

changing fuel types. Some jurisdictions require

the use of a liner even when the same fuel is used.

At a minimum, the chimney shall be examined

by a qualified person in accordance with the

requirements of Chapter 11 of NFPA 211, Standard

for Chimneys, Fireplaces, Vents, and Solid Fuel-

Burning Appliances.

SECTION V: VENTING & AIR INTAkE PIPING

a. Loose Mortar – Loose mortar could be an

indication of a prior history of condensing flue

gases upon the inside walls of the chimney.

Colder climates are more susceptible to this

condition. Under no circumstances shall a

chimney of this condition be used until it meets

the requirements of NFPA 211.

b. Unlined Chimney – Under no circumstances

shall a chimney constructed of brick only

be used. Only approved clay liners or listed

chimney lining systems shall be used as specified

in NFPA 31.

c. Abandoned Openings – Openings through the

chimney wall that are no longer used shall

be sealed in accordance to NFPA 211. Often

abandoned openings are improperly sealed and

usually covered by a gypsum wall covering.

d. Clean Chimney – Chimney shall be free of all

loose debris.

5. Draft Regulator – the draft regulator supplied with

the boiler must be used with this appliance. No

other draft regulator shall be used. Refer to Figures

15 and 16.

B. CHIMNEY CONNECTOR

1. A chimney connector (vent pipe) is used to connect

the boiler to the base of the chimney. The chimney

connector should be kept as short as possible. The

horizontal length of the chimney connector shall not

be greater than 10 feet.

NOTE: Secure chimney connector to cast iron

smokebox collar with three (3) #10 x ½" self drilling

hex head TEK screws provided in appropriate

Parts Carton. Locate screws around perimeter of

connector as shown in Figure 15 and approximately

½" in from edge. Use drill with 5/16" hex bit to

drive screws through connector and smokebox

collar.

DANGER

The chimney and connector shall be inspected

annually for signs of debris and corrosion.

Loose mortar at the base of the chimney may be

a sign of condensate damage to the chimney.

A chimney professional shall be contacted

immediately to examine the damage and

recommend a solution. Long term operation

while in this condition may cause a venting

failure and force flue gases into the living

space. If the chimney is to be relined use the

recommendations in NFPA 31, Appendix E.

This manual is related to the following products: