by drawing a small sample of boiler water and

testing with hydrion paper which is used in the

same manner as litmus paper, except it gives

specific readings. A color chart on the side of

the small hydrion dispenser gives the reading in

pH. Hydrion paper is inexpensive and obtainable

from any chemical supply house or through your

local druggist. The pH should be higher than

7, but lower than 11. Add some of the washout

chemical (caustic soda), if necessary, to bring the

pH within the specified range.

f. Boiler is now ready to be put into service.

C. ExCESSIVE MAkE-UP wATER

IMPORTANT

IF, DURING NORMAL OPERATION, IT IS

NECESSARy TO ADD MORE WATER THAN

INDICATED BELOW, CONSULT A QUALIFIED

SERVICE TECHNICIAN TO CHECK yOUR

SySTEM FOR LEAKS.

EXCESSIVE WATER ADDITION:

(Gallons / Month)

MST88: 6

MST396: 8

MST513: 9½

MST69: 11

A leaky system will increase the volume of make-up

water supplied to the boiler, which can significantly

shorten the life of the boiler. Entrained in make-up

water are dissolved minerals, salts and oxygen. When

the fresh, cool make-up water is heated in the boiler, the

minerals fall out as sediment, the salts coat the inside

of the boiler, and the oxygen escapes as a gas. The

accumulation of sediment eventually isolates the water

from contacting the cast iron. When this happens the

cast iron in that area gets extremely hot and eventually

cracks. The presence of free oxygen or chloride salts

in the boiler corrodes the cast iron from the inside.

More make-up water and higher concentrations of

contaminants damage the boiler sooner. Our warranty

does not cover oxygen corrosion and sediment-

related damage. Clearly it is in everyone’s best

interest to prevent this type of failure. You can do your

part by ensuring that your system is leak-free.

D. ATTENTION TO BOILER wHILE NOT IN

OPERATION.

NOTICE

If boiler is not used during winter time, it must be

fully drained to prevent freeze damage.

1. Spray inside surfaces with light lubricating or

crankcase oil using gun with extended stem so as to

reach all corners.

2. With steam boilers, at end of season add sufficient

water to fill boiler to top of water column and leave

it that way until fall when water should be drained

again to proper level. If at this time boiler water is

dirty, drain water, flush out boiler, and refill with

clean water to prescribed water level.

3. Always keep the manual fuel supply valve shut off

if the burner is shut down for an extended period of

time.

4. To recondition the heating system in the fall season

after a prolonged shut down, follow the instructions

outlined in Section VIII, Paragraphs A through J.

WARNING

This boiler contains controls which may cause the

boiler to shut down and not restart without service.

If damage due to frozen pipes is a possibility, the

heating system should not be left unattended

in cold weather; or appropriate safeguards and

alarms should be installed on the heating system

to prevent damage if the boiler is inoperative.