ii. Check Safety Features

Safe Start:

Place a jumper across cad cell terminals.

Follow procedure to turn on burner.

Burner must not start, indicator light turns

on and control remains in Idle Mode.

Remove jumper.

iii. Simulate Ignition or Flame Failure:

Follow procedure to turn on burner.

Close hand valve in oil supply line.

Failure occurs, device enters Recycle

Mode. Indicator light flashes at ¼ Hz rate

2 seconds on, 2 seconds off).

Device tries to restart system after

approximately 60 seconds.

After third Recycle Mode trial, safety

switch locks out within safety switch

timing indicated on label and control

enters Restricted Mode. Indicator light

flashes at 1 Hz rate (½ second on, ½

second off). Ignition and motor stop and

oil valves closes.

Figure 6: Cad Cell Location

If safety switch shuts down burner and

resistance is above 1600 OHMS, open line

switch to boiler. Access cad cell under

ignitor, clean face of cad cell and see that

cell is securely in socket. Check gasket

around perimeter of ignitor lid for proper

seal. If gasket is missing or damaged,

replace gasket. Room light can effect cad

cell resistance. Reset safety switch.

Close line switch to boiler. If burner starts

and runs beyond safety switch cut-off

time, cell is good. If not, install new cell.

v. Power Failure Check: After Flame is

established, turn the power off to the control/

burner. The burner should shut down safely.

When power is restored a normal ignition

sequence should be started.

3. WARNING — Check Pressure Limit Control

— Jumper Thermostat Terminals. Allow burner to

operate until shut-down by limit. Installation is not

considered complete until this check has been made.

WARNING

Jumper must be removed after this check.

4. Check low water cut off control with water level at

normal water line (see Figure 1). Raise thermostat

setting to allow burner to operate. Open boiler drain

to allow water level to drop to bottom of sight glass

until burner operation is shut-down by low water

cut-off.

Close boiler drain and refill to normal water line.

Burner should automatically restart during fill.

Lower thermostat setting.

5. Check operating control on boiler equipped with

tankless heaters. With burner off, draw hot water

until burner starts, then turn off hot water and check

burner shut-down.

J. IF CONTROLS DO NOT MEET

REqUIREMENTS outlined in Paragraph I.,

replace control and repeat checkout procedures.

iv.

Cad Cell Check: See Figure 26.

Perform cad cell resistance check as

outlined in control feature. If resistance is

below 1600 OHMS and burner runs

beyond safety cut-out time, cad cell is

good.