SECTION VIII: SYSTEM START-UP

1. SET ROOM THERMOSTAT about 10° above

room temperature.

2. PRESS RED RESET BUTTON on front of

burner cover, hold for one (1) second and release to

reset primary control.

3. On STEAM BOILERS:

a. With an L404F1367 - set cut-out pressure

(MAIN scale) on the pressure limit for (1) PSI

and differential pressure (DIFF.) for .5 PSI.

These pressures may be varied to suit individual

requirements of the system.

4. On STEAM BOILERS WITH TANKLESS

DOMESTIC WATER HEATERS, set boiler

water temperature dial on L4006 operating control

at 190°F (max.). Set differential at 10°.

E. ADJUST OIL BURNER BEFORE

STARTING.
1. CHECK BURNER AIR BAND, AIR SHUTTER

AND HEAD SETTING (if applicable), readjust if

necessary, see Table 8 at rear of manual.

2. OPEN ALL OIL LINE VALVES.
3. Attach a plastic hose to fuel pump vent fitting and

provide a pan to catch the oil.

4. OPEN FLAME OBSERVATION PORT COVER

on burner swing door.

F. START OIL BURNER.

1. Open vent fitting on fuel pump.
2. PRESS RED RESET BUTTON on front of burner

cover, hold for one (1) second and release to reset

primary control.

3. TURN ‘ON’ BURNER service switch and

allow burner to run until oil flows from vent

fitting in a SOLID stream without air bubbles for

approximately 10 seconds.

NOTE: For Primary Control "Pump Priming

Cycle" details, see Paragraph I, No. 2., Step a.,

Item ii .

4. Close vent fitting and burner flame should start

immediately after prepurge is completed. Prepurge

prevents burner flame until 15 seconds has elapsed

after initial power is applied to burner. During

prepurge the motor and igniter will operate but the

oil valve will remain closed. Refer to Oil Primary

Control Instructions for more details.

A. ALwAYS INSPECT INSTALLATION

BEFORE STARTING BURNER.
1. Verify that the venting, water piping, oil piping, and

electrical system are installed properly. Refer to

Installation Instructions contained in this manual.

2. Confirm all electrical, water and oil supplies are

turned off at the source and that the vent is clear

from obstructions.

WARNING

Completely read, understand and follow all

instructions in this manual before attempting

start up.

B

.

FILL HEATING SYSTEM wITH wATER.

NOTICE

It is important, especially in a steam system, to

properly remove the oil and dirt from the system.

Failure to clean the system can result in erratic

water lines and surging.

CLEAN HEATING SYSTEM if boiler water or

condensate return water is dirty or if erratic water lines

or surging exist after a few days of boiler operation.

Refer to Maintenance and Service Instructions Section

of this manual for proper cleaning instructions for

steam and water boilers.
1. STEAM BOILERS — Fill boiler to normal water

line. Refer to Figure No. 1.

WARNING

The maximum operating pressure of this boiler is

posted on the ASME Data Label located on the top

of the boiler. Never exceed this pressure. Do not

plug relief valve.

C. CHECk CONTROLS, wIRING AND

BURNER to be sure that all connections are tight and

burner is rigid, that all electrical connections have been

completed and fuses installed, and that oil tank is filled

and oil lines have been tested.

D. SET CONTROLS with burner service switch turned

“OFF”.

WARNING

All boilers equipped with burner swing door have a potential hazard which can cause severe property damage,

personal injury or loss of life if ignored. Before opening swing door, turn off service switch to boiler to

prevent accidental firing of burner outside the combustion chamber. Be sure to tighten swing door fastener

completely when service is completed.