beautypg.com

Burnham MEGASTEAM MST288 User Manual

Page 40

background image

40

BOILER SEQUENCE OF OPERATION WITH PROBE LWCO (See Figure 18)

When the thermostat calls for heat, it energizes the R8285C Control Center relay which in turn energizes the cad cell

primary control, bringing on the burner. The burner will operate in the following sequence: Prepurge for the first 10

seconds; fire until the thermostat is satisfied or the limit setting on the high limit is reached; post-purge for the last 10

seconds. When the pressure limit control restores the circuit on a drop in pressure, the burner will start if the thermo-

stat is still calling for heat.
The probe low water cut-off will shut down the burner after a 10-15 second delay, if the water level in the boiler drops

below the probe level.
The Hydrolevel CG450 low water cut-off will shut down the burner for 90 seconds every 10 minutes of firing time to

allow water level to stabilize. If the water level is too low the burner will not be allowed to restart.
The probe low water cut-off will reset and restart the burner with a call for heat a few seconds after the water is re-

turned to its normal level.
On burner start, if the cad cell does not see flame within approximately 15 seconds, primary control will shut burner

down and enter into a recycle mode, after 60 seconds burner will restart and repeat trial for ignition. If after three

(3) trials for ignition, flame is not detected, control will enter into restricted mode and must be reset manually before

burner can be restarted.
When there is no demand for heat, the operating control will maintain the boiler water temperature at the selected

setting for proper operation of the domestic water heater, if equipped with optional tankless heater.

BOILER SEQUENCE OF OPERATION WITH PROBE LWCO (See Figure 19)
When the thermostat calls for heat, it energizes the R8285C Control center relay, which in

turn energizes the cad cell primary control, bringing on the burner. The burner will

operate in the following sequence: Prepurge for the first 10 seconds; fire until the

thermostat is satisfied or the limit setting on the high limit is reached; post-purge

for the last 10 seconds. When the pressure limit control restores the circuit on a

drop in pressure, the burner will start if the thermostat is still calling for heat.

The probe low water cut-off will shut down the burner after a 10-15 second delay, if

the water level in the boiler drops below the probe level.

The probe low water cut-off will reset and restart the burner with a call for heat a

few seconds after the water is returned to its normal level.

On burner start, if the cad cell does not see flame within approximately 15 sec-

onds, primary control will shut burner down and enter into a recycle mode, after 60

seconds burner will restart and repeat trial ignition. If after three (3) trials for igni-

tion, flame is not detected, control will enter into restricted mode and must be reset

manually before burner can be restarted.

When there is no demand for heat, the operating control will maintain the boiler

water temperature at the selected setting for proper operation of the domestic

water heater, if equipped with optional tankless heater.

BOILER SEQUENCE OF OPERATION WITH FLOAT LWCO (See Figure 0)

When the thermostat calls for heat, it energizes the R8285C Control center relay, which in turn energizes the cad cell

primary control, bringing on the burner. The burner will operate in the following sequence: Prepurge for the first 10

seconds; fire until the thermostat is satisfied or the limit setting on the high limit is reached; post-purge for the last 10

seconds. When the pressure limit control restores the circuit on a drop in pressure, the burner will start if the thermo-

stat is still calling for heat. The low water cut-off will shut down the burner if the water level in the boiler drops too low.

The control resets and restarts the burner with a call for heat a few seconds after the water is returned to its normal

level.
On burner start, if the cad cell does not see flame within approximately 15 seconds, primary control will shut burner

down and enter into a recycle mode, after 60 seconds burner will restart and repeat trial for ignition. If after three

(3) trials for ignition, flame is not detected, control will enter into restricted mode and must be reset manually before

burner can be restarted.
When there is no demand for heat, the operating control will maintain the boiler water temperature at the selected set-

ting for proper operation of the domestic water heater, if equipped with optional tankless heater.

McDonnell & Miller PS-801

Terminals May be Lettered or

Numbered as Follows:

Wire

Color

Numbered

Terminals

Lettered

Terminals

RD

5

B

BK

1

H

WH

2

N

Jumper

1-3

H-C

This manual is related to the following products: