PERFORMANCE DATA (cont)

GENERAL NOTES FOR FAN PERFORMANCE DATA TABLES

1. Values include losses for filters, unit casing, and wet coils. See this

page for accessory/FIOP static pressure information.

2. Extensive motor and electrical testing on these units ensures that

the full range of the motor can be utilized with confidence. Using fan
motors up to the wattage ratings shown will not result in nuisance
tripping or premature motor failure. Unit warranty will not be

affected. See Evaporator-Fan Motor Performance table on page 73
for additional information.

3. Use of a field-supplied motor may affect wire sizing. Contact your

Bryant representative for details.

4. Interpolation is permissible. Do not extrapolate. (Belt drive units

only.)

OUTDOOR SOUND POWER (Total Unit)

NOTE: Indoor sound power is available in Bryant’s Electronic Catalog program (ECAT) for specific operating parameters.

ACCESSORY/FIOP ECONOMIZER IV AND ECONOMI$ER2 STATIC PRESSURE* (in. wg) — 580F036-073

LEGEND

*The static pressure must be added to external static pressure. The

sum and the evaporator entering-air cfm should be used in conjunction
with the Fan Performance tables to determine indoor blower rpm and
watts.

ACCESSORY/FIOP ECONOMISER IV AND ECONOMI$ER2 STATIC PRESSURE* (in. wg) — 580F090-151

LEGEND

*The static pressure must be added to external static pressure. The

sum and the evaporator entering-air cfm should then be used in con-
junction with the Fan Performance tables to determine blower rpm and
watts.

UNIT 580F

SOUND

RATING

60 Hz (dB)

A-WEIGHTED

(dB)

OCTAVE BANDS

63

125

250

500

1000

2000

4000

8000

036-072

81

80.5

56.8

75.8

72.4

72.9

74.8

75.4

71.3

69.1

073

80

80.0

59.1

68.9

68.7

71.9

74.0

68.9

65.7

59.0

090

87

86.4

83.2

87.4

83.5

82.8

83.0

77.7

71.8

67.0

091, 103

82

82.0

62.2

69.3

71.5

74.7

76.2

72.9

68.7

61.5

120

88

87.6

97.6

90.4

85.7

84.8

83.9

77.5

71.3

65.8

121

84

84.0

64.6

71.7

73.3

76.9

77.6

73.7

70.6

63.7

150

87

86.4

83.7

87.2

83.4

82.8

83.0

77.7

71.8

67.0

151

86

86.0

63.7

69.9

72.5

78.2

81.1

77.3

73.3

66.8

COMPONENT

CFM

1250

1500

1750

2000

2250

2500

2750

3000

Vertical EconoMi$er IV and EconoMi$er2

0.045

0.065

0.08

0.12

0.145

0.175

0.22

0.255

Horizontal EconoMi$er IV and EconoMi$er2

0.1

0.125

0.15

0.18

0.225

0.275

FIOP — Factory-Installed Option

COMPONENT

CFM

2250

2500

2750

3000

3250

3500

3750

4000

4250

4500

4750

5000

5250

6250

Vertical EconoMi$er IV
and EconoMi$er2

0.06

0.075

0.09

0.115

0.13

0.15

0.17

0.195

0.22

0.25

0.285

0.325

0.36

Horizontal EconoMi$er IV
and EconoMi$er2

0.1

0.125

0.15

0.18

0.21

0.25

0.275

0.3

0.34

0.388

FIOP — Factory-Installed Option

58

0F0

3

6

-15

1