beautypg.com

216 performance data (cont) – Bryant 581A/B User Manual

Page 216

background image

216

PERFORMANCE DATA (cont)

COOLING CAPACITIES, UNITS WITH HOT GAS REHEAT OPTION (cont)

LEGEND

NOTES:

1. Direct interpolation is permissible. Do not extrapolate.
2. The following formulas may be used:

t

lwb

= Wet-bulb temperature corresponding to enthalpy of air leaving evapo-

rator coil (h

lwb

)

Where: h

ewb

= Enthalpy of air entering evaporator coil

3. The SHC is based on 80 F edb temperature of air entering evaporator coil.

Below 80 F edb, subtract (corr factor x cfm) from SHC.
Above 80 F edb, add (corr factor x cfm) to SHC.

Interpolation is permissible.
Correction Factor = 1.10 x (1 – BF) x (edb – 80).

581A240 (20 TONS) UNIT WITH HOT GAS REHEAT — A IN REHEAT, B AND C OFF

Temp (F)

Air Entering

Condenser

(Edb)

Evaporator Air Quantity — Cfm/BF

6000/0.04

7000/0.05

8000/0.06

9000/0.07

10,000/0.08

Evaporator Air — Relative Humidity (%)

50

55

60

50

55

60

50

55

60

50

55

60

50

55

60

65

TC

73

75

77

73

76

78

74

76

79

75

77

79

75

78

80

SHC

45

42

40

47

44

42

49

47

44

51

48

46

53

50

48

kW

6.1

6.1

6.1

6.1

6.1

6.1

6.1

6.1

6.1

6.1

6.1

6.1

6.1

6.1

6.1

75

TC

55

57

59

56

58

60

56

58

60

57

59

61

57

59

61

SHC

29

25

22

31

27

24

33

30

26

35

31

28

37

33

30

kW

6.6

6.6

6.6

6.6

6.6

6.6

6.6

6.6

6.6

6.6

6.6

6.6

6.6

6.6

6.6

85

TC

38

40

41

38

40

42

39

40

42

39

41

42

39

41

43

SHC

13

8

4

15

10

7

17

13

9

19

14

10

21

16

12

kW

7.2

7.2

7.2

7.2

7.2

7.2

7.2

7.2

7.2

7.2

7.2

7.2

7.2

7.2

7.2

95

TC

20

22

23

21

22

24

21

22

24

21

23

24

21

23

24

SHC

–4

–9

–14

–1

–7

–11

1

–4

–9

3

–3

–7

5

–1

–6

kW

7.7

7.7

7.7

7.7

7.7

7.7

7.7

7.7

7.7

7.7

7.7

7.7

7.7

7.7

7.7

581A240 (20 TONS) UNIT WITH HOT GAS REHEAT — A AND B IN REHEAT, C OFF

Temp (F)

Air Entering

Condenser

(Edb)

Evaporator Air Quantity — Cfm/BF

6000/0.04

7000/0.05

8000/0.06

9000/0.07

10,000/0.08

Evaporator Air — Relative Humidity (%)

50

55

60

50

55

60

50

55

60

50

55

60

50

55

60

65

TC

106

110

113

108

111

114

109

113

116

110

114

117

111

115

118

SHC

45

42

39

47

44

41

49

46

44

51

48

46

53

50

47

kW

10.7

10.7

10.8

10.7

10.7

10.8

10.7

10.7

10.8

10.7

10.7

10.8

10.7

10.7

10.8

75

TC

81

84

87

82

85

88

83

86

89

83

87

89

84

87

90

SHC

29

25

21

31

27

24

34

29

26

36

31

28

37

33

30

kW

11.6

11.6

11.6

11.6

11.6

11.6

11.6

11.6

11.6

11.6

11.6

11.6

11.6

11.6

11.6

85

TC

56

58

61

56

59

61

56

59

61

57

59

62

57

60

62

SHC

13

8

3

16

10

6

18

13

8

20

15

10

22

16

12

kW

12.6

12.7

12.7

12.6

12.7

12.7

12.6

12.7

12.7

12.6

12.7

12.7

12.6

12.7

12.7

95

TC

30

33

34

30

32

34

30

32

34

30

32

34

30

32

34

SHC

–3

–9

–14

0

–6

–12

2

–4

–10

4

–2

–8

6

0

–6

kW

13.6

13.6

13.6

13.6

13.6

13.6

13.6

13.6

13.6

13.6

13.6

13.6

13.6

13.6

13.6

581A240 (20 TONS) UNIT WITH HOT GAS REHEAT — A AND B IN REHEAT, C ON

Temp (F)

Air Entering

Condenser

(Edb)

Evaporator Air Quantity — Cfm/BF

6000/0.04

7000/0.05

8000/0.06

9000/0.07

10,000/0.08

Evaporator Air — Relative Humidity (%)

50

55

60

50

55

60

50

55

60

50

55

60

50

55

60

65

TC

177

185

191

177

185

192

178

186

192

178

186

193

178

186

193

SHC

98

92

86

100

94

88

101

95

90

103

97

92

104

98

93

kW

14.5

14.6

14.7

14.5

14.6

14.7

14.5

14.6

14.7

14.5

14.6

14.7

14.5

14.6

14.7

75

TC

154

161

168

154

162

169

155

162

169

155

163

169

155

163

170

SHC

81

73

66

83

75

69

85

78

71

87

80

73

89

81

75

kW

16.1

16.1

16.1

16.1

16.1

16.1

16.1

16.1

16.1

16.1

16.1

16.1

16.1

16.1

16.1

85

TC

131

138

145

131

139

145

131

139

146

132

139

146

132

140

146

SHC

63

54

46

66

57

49

69

60

52

71

62

54

73

64

56

kW

17.7

17.7

17.8

17.7

17.7

17.8

17.7

17.7

17.8

17.7

17.7

17.8

17.7

17.7

17.8

95

TC

107

115

122

108

115

122

108

116

122

108

116

123

109

116

123

SHC

46

35

25

50

39

29

53

42

32

55

45

35

58

47

38

kW

19.3

19.3

19.3

19.3

19.3

19.3

19.3

19.3

19.3

19.3

19.3

19.3

19.3

19.3

19.3

BF

Bypass Factor

Edb — Entering Dry-Bulb
Ewb — Entering Wet-Bulb
kW

Compressor Motor Power Input

ldb

Leaving Dry-Bulb

lwb

Leaving Wet-Bulb

SHC — Sensible Heat Capacity (1000 Btuh) Gross
TC

Total Capacity (1000 Btuh) Gross

t

ldb

= t

edb

sensible capacity (Btuh)

1.10 x cfm

h

lwb

= h

ewb

total capacity (Btuh)

4.5 x cfm

BYPASS
FACTOR

(BF)

ENTERING AIR DRY-BULB TEMP (F)

79

78

77

76

75

under 75

81

82

83

84

85

over 85

Correction Factor

.05

1.04

2.07

3.11

4.14

5.18

Use formula

shown below.

.10

.98

1.96

2.94

3.92

4.90

.20

.87

1.74

2.62

3.49

4.36

.30

.76

1.53

2.29

3.05

3.82

581

A155

-3

00