PERFORMANCE DATA (cont)
COOLING CAPACITIES — STANDARD UNITS (cont)
LEGEND
NOTES:
1. Direct interpolation is permissible. Do not extrapolate.
2. The following formulas may be used:
tlwb = Wet-bulb temperature corresponding to enthalpy of air leaving evapo-
rator coil (hlwb)
Where: hewb = Enthalpy of air entering evaporator coil
3. The SHC is based on 80 F edb temperature of air entering evaporator coil.
Below 80 F edb, subtract (corr factor x cfm) from SHC.
Above 80 F edb, add (corr factor x cfm) to SHC.
Interpolation is permissible.
Correction Factor = 1.10 x (1 – BF) x (edb – 80).
4. Use chart below for bypass factor.
581A210 (18 Tons)
Temp (F)
Air Ent
Cond
Evap Air — Cfm/BF
5400/0.05
6300/0.06
7200/0.07
Evap Air — Ewb (F)
54
58
62
67
72
76
80
54
58
62
67
72
76
80
54
58
62
67
72
76
80
60
TC
202
206
211
229
248
263
279
212
215
218
235
254
269
285
220
221
223
239
259
273
289
SHC
202
193
184
155
124
99.3
74.7
212
205
199
166
131
103
74.9
220
216
213
177
138
106
75
kW
10.2
10.3
10.4
10.6
10.8
11
11.2
10.4
10.4
10.4
10.7
10.9
11.1
11.3
10.5
10.5
10.5
10.7
11
11.2
11.4
70
TC
197
202
206
223
242
256
272
207
209
212
228
247
262
277
215
216
217
233
252
267
282
SHC
197
189
181
152
122
97
72.5
207
202
196
163
129
101
72.7
215
212
210
174
135
104
72.8
kW
11.4
11.5
11.5
11.8
12
12.2
12.5
11.6
11.6
11.6
11.9
12.1
12.3
12.6
11.7
11.7
11.7
11.9
12.2
12.4
12.6
75
TC
195
199
203
219
238
253
268
204
206
209
225
244
258
273
212
213
214
229
248
263
277
SHC
195
187
180
150
120
95.8
71.3
204
199
195
162
127
99.3
71.4
212
210
208
173
134
103
71.5
kW
12.1
12.2
12.2
12.5
12.7
13
13.2
12.3
12.3
12.3
12.6
12.8
13
13.3
12.4
12.4
12.4
12.6
12.9
13.1
13.3
85
TC
190
193
196
213
231
246
260
199
201
202
218
236
251
264
206
207
208
222
240
255
268
SHC
190
183
177
148
118
93.4
68.8
199
195
191
159
125
96.9
68.9
206
205
204
170
131
100
69
kW
13.5
13.5
13.6
13.8
14.1
14.4
14.6
13.6
13.7
13.7
13.9
14.2
14.5
14.7
13.7
13.8
13.8
14
14.3
14.5
14.8
95
TC
184
187
190
205
222
236
250
193
194
195
210
227
241
254
200
200
201
214
231
245
258
SHC
184
179
173
144
114
90.2
65.9
193
190
187
156
121
93.7
66.1
200
199
199
167
128
97.1
66.2
kW
15
15
15.1
15.4
15.7
15.9
16.2
15.1
15.2
15.2
15.5
15.8
16
16.3
15.3
15.3
15.3
15.5
15.8
16.1
16.3
105
TC
178
180
182
197
213
228
240
186
187
188
201
217
232
244
193
193
193
205
221
235
247
SHC
178
173
169
141
111
87.3
62.9
186
184
183
152
118
90.8
63.1
193
193
193
163
124
94.1
63.2
kW
16.6
16.7
16.7
17
17.3
17.7
17.9
16.8
16.8
16.8
17.1
17.4
17.8
18
16.9
16.9
16.9
17.2
17.5
17.8
18
115
TC
171
172
174
188
203
217
228
179
179
179
192
207
221
232
185
185
185
195
210
224
235
SHC
171
168
165
137
107
83.6
59.6
179
178
178
149
114
87.1
59.7
185
185
185
159
121
90.4
59.9
kW
18.4
18.4
18.4
18.8
19.1
19.4
19.7
18.6
18.6
18.6
18.9
19.2
19.5
19.8
18.7
18.7
18.7
19
19.3
19.6
19.9
125
TC
164
165
165
178
192
205
216
171
171
171
182
196
208
219
177
177
177
185
199
211
222
SHC
164
162
160
134
104
79.8
56.1
171
171
171
145
110
83.2
56.3
177
177
177
155
117
86.5
56.4
kW
20.2
20.3
20.3
20.6
21
21.3
21.6
20.4
20.4
20.4
20.8
21.1
21.4
21.7
20.6
20.6
20.6
20.8
21.2
21.5
21.8
581A210 (18 Tons) (cont)
Temp (F)
Air Ent
Cond
Evap Air — Cfm/BF
8100/0.08
9000/0.09
Evap Air — Ewb (F)
54
58
62
67
72
76
80
54
58
62
67
72
76
80
60
TC
227
227
228
243
262
277
293
233
233
233
246
265
280
295
SHC
227
226
224
187
144
109
75.1
233
233
233
198
151
113
75.1
kW
10.5
10.6
10.6
10.7
11
11.2
11.4
10.6
10.6
10.6
10.8
11
11.3
11.5
70
TC
222
222
222
236
255
271
284
228
228
227
239
258
272
287
SHC
222
221
221
185
142
107
72.8
228
228
227
195
148
110
72.9
kW
11.8
11.8
11.8
12
12.2
12.5
12.7
11.9
11.9
11.8
12
12.3
12.5
12.7
75
TC
219
219
219
232
251
266
280
225
224
224
235
254
268
282
SHC
219
218
218
183
140
106
71.6
225
224
224
193
147
109
71.7
kW
12.5
12.5
12.5
12.7
12.9
13.2
13.4
12.6
12.5
12.5
12.7
13
13.2
13.4
85
TC
213
213
213
225
243
258
271
218
218
218
228
245
260
273
SHC
213
213
213
180
138
103
69.1
218
218
218
190
144
107
69.2
kW
13.8
13.8
13.8
14.1
14.3
14.6
14.8
13.9
13.9
13.9
14.1
14.4
14.6
14.8
95
TC
206
206
206
217
234
248
260
211
211
211
220
236
250
262
SHC
206
206
206
177
134
100
66.3
211
211
211
187
141
103
66.4
kW
15.4
15.4
15.4
15.6
15.9
16.1
16.4
15.5
15.5
15.5
15.6
15.9
16.2
16.4
105
TC
199
199
199
208
224
238
249
203
203
204
210
226
240
251
SHC
199
199
199
173
131
97.2
63.2
203
203
204
183
137
100
63.4
kW
17
17.1
17.1
17.3
17.6
17.9
18.1
17.2
17.2
17.2
17.3
17.6
17.9
18.1
115
TC
191
191
191
198
213
226
237
195
195
195
201
215
228
238
SHC
191
191
191
169
127
93.5
60
195
195
195
179
133
96.6
60
kW
18.8
18.8
18.8
19
19.3
19.7
19.9
18.9
18.9
18.9
19.1
19.4
19.7
19.9
125
TC
182
182
182
188
201
213
224
186
186
186
190
203
215
225
SHC
182
182
182
165
123
89.6
56.5
186
186
186
174
129
92.6
56.6
kW
20.7
20.7
20.7
20.9
21.2
21.6
21.9
20.9
20.9
20.9
21
21.3
21.6
21.9
BF
— Bypass Factor
Edb — Entering Dry-Bulb
Ewb — Entering Wet-Bulb
kW
— Compressor Motor Power Input
ldb
— Leaving Dry-Bulb
lwb
— Leaving Wet-Bulb
SHC — Sensible Heat Capacity (1000 Btuh) Gross
TC
— Total Capacity (1000 Btuh) Gross
tldb = tedb –
sensible capacity (Btuh)
1.10 x cfm
hlwb = hewb –
total capacity (Btuh)
4.5 x cfm
BYPASS
FACTOR
(BF)
ENTERING AIR DRY-BULB TEMP (F)
79
78
77
76
75
under 75
81
82
83
84
85
over 85
Correction Factor
.05
1.04
2.07
3.11
4.14
5.18
Use formula
shown below.
.10
.98
1.96
2.94
3.92
4.90
.20
.87
1.74
2.62
3.49
4.36
.30
.76
1.53
2.29
3.05
3.82
CFM
ENTERING WET-BULB (F)
54
58
62
67
72
76
80
Bypass Factor
5400
0.424
0.238
0.125
0.120
0.138
0.000
0.000
6300
0.478
0.304
0.153
0.132
0.145
0.000
0.000
7200
0.525
0.364
0.190
0.144
0.153
0.000
0.000
8100
0.562
0.414
0.231
0.156
0.162
0.000
0.000
9000
0.594
0.456
0.281
0.168
0.170
0.000
0.000
581
A155
-3
00