beautypg.com

214 performance data (cont) – Bryant 581A/B User Manual

Page 214

background image

214

PERFORMANCE DATA (cont)

COOLING CAPACITIES, UNITS WITH HOT GAS REHEAT OPTION (cont)

LEGEND

NOTES:

1. Direct interpolation is permissible. Do not extrapolate.
2. The following formulas may be used:

t

lwb

= Wet-bulb temperature corresponding to enthalpy of air leaving evapo-

rator coil (h

lwb

)

Where: h

ewb

= Enthalpy of air entering evaporator coil

3. The SHC is based on 80 F edb temperature of air entering evaporator coil.

Below 80 F edb, subtract (corr factor x cfm) from SHC.
Above 80 F edb, add (corr factor x cfm) to SHC.

Interpolation is permissible.
Correction Factor = 1.10 x (1 – BF) x (edb – 80).

581A181 (15 TONS) UNIT WITH HOT GAS REHEAT — A AND B IN REHEAT, C ON

Temp (F)

Air Entering

Condenser

(Edb)

Evaporator Air Quantity — Cfm/BF

4500/0.12

5250/0.14

6000/.015

6750/0.18

7500/0.18

Evaporator Air — Relative Humidity (%)

50

55

60

50

55

60

50

55

60

50

55

60

50

55

60

65

TC

133

140

146

134

141

147

135

142

148

136

143

149

137

144

150

SHC

73

69

65

75

71

67

77

73

69

79

75

71

81

76

72

kW

10.7

10.7

10.8

10.7

10.7

10.8

10.7

10.7

10.8

10.7

10.7

10.8

10.7

10.7

10.8

75

TC

116

123

128

117

123

129

117

124

130

118

125

131

118

126

132

SHC

61

55

50

63

57

52

65

59

54

66

61

56

68

62

57

kW

11.8

11.8

11.8

11.8

11.8

11.8

11.8

11.8

11.8

11.8

11.8

11.8

11.8

11.8

11.8

85

TC

98

105

111

99

106

112

99

106

112

100

107

113

100

107

113

SHC

48

41

35

50

43

37

52

45

39

54

46

40

55

48

42

kW

12.9

13.0

13.0

12.9

13.0

13.0

12.9

13.0

13.0

12.9

13.0

13.0

12.9

13.0

13.0

95

TC

81

88

94

81

88

94

81

88

95

81

89

95

81

89

95

SHC

36

28

21

38

29

22

39

31

24

41

32

25

42

34

26

kW

14.0

14.1

14.1

14.0

14.1

14.1

14.0

14.1

14.1

14.0

14.1

14.1

14.0

14.1

14.1

581A210 (18 TONS) UNIT WITH HOT GAS REHEAT IN COOLING MODE

Temp (F)

Air Entering

Condenser

(Edb)

Air Entering Evaporator — Cfm/BF

5400/0.03

6300/0.04

7200/0.05

8100/0.06

9000/0.07

Air Entering Evaporator — Ewb (F)

57

62

67

72

57

62

67

72

57

62

67

72

57

62

67

72

57

62

67

72

75

TC

183

198

215

236

192

206

224

245

201

212

230

252

210

216

235

257

217

222

240

262

SHC

182

169

143

120

192

184

156

127

201

197

166

134

210

209

177

141

217

218

186

147

kW

11.5

11.7

11.9

12.2

11.6

11.8

12.1

12.4

11.7

11.9

12.2

12.5

11.9

11.9

12.2

12.5

12.0

12.0

12.3

12.6

85

TC

179

192

210

231

188

200

217

239

197

205

223

244

205

210

227

249

212

215

232

254

SHC

179

166

142

117

188

181

153

125

197

194

163

131

205

206

173

138

212

213

183

145

kW

12.8

13.1

13.3

13.7

13.0

13.2

13.5

13.8

13.2

13.3

13.6

13.9

13.3

13.4

13.7

14.0

13.4

13.5

13.7

14.1

95

TC

175

186

202

223

184

193

209

229

193

198

215

236

200

203

219

241

206

208

223

245

SHC

175

163

142

114

184

177

151

121

193

191

160

128

200

200

170

135

206

207

180

142

kW

14.1

14.3

14.6

14.9

14.3

14.4

14.7

15.1

14.4

14.5

14.8

15.2

14.6

14.6

14.9

15.3

14.7

14.7

15.0

15.4

105

TC

170

180

197

215

179

186

201

222

187

192

208

226

194

197

212

230

200

202

215

235

SHC

170

160

136

111

179

174

147

118

187

186

158

125

194

195

168

131

200

201

178

138

kW

15.6

15.8

16.1

16.5

15.8

15.9

16.2

16.6

15.9

16.0

16.3

16.7

16.1

16.1

16.4

16.8

16.2

16.2

16.5

16.9

115

TC

165

173

189

208

173

179

195

214

181

184

199

218

187

189

203

222

193

194

205

225

SHC

165

157

133

109

173

170

144

116

181

181

154

122

187

188

164

128

193

194

173

134

kW

17.2

17.4

17.7

18.1

17.4

17.5

17.8

18.2

17.5

17.6

17.9

18.3

17.7

17.7

18.0

18.4

17.8

17.9

18.1

18.5

125

TC

159

166

181

199

167

171

186

203

174

177

190

207

180

182

193

210

186

187

196

213

SHC

159

154

130

105

167

166

140

112

174

175

151

118

180

181

160

124

186

187

170

130

kW

18.9

19.1

19.5

19.9

19.1

19.2

19.6

20.0

19.3

19.4

19.7

20.1

19.5

19.5

19.8

20.1

19.6

19.6

19.8

20.2

581A210 (18 TONS) UNIT WITH HOT GAS REHEAT — A IN REHEAT, B AND C OFF

Temp (F)

Air Entering

Condenser

(Edb)

Evaporator Air Quantity — Cfm/BF

5400/0.03

6300/0.04

7200/0.05

8100/0.06

9000/0.07

Evaporator Air — Relative Humidity (%)

50

55

60

50

55

60

50

55

60

50

55

60

50

55

60

65

TC

61

63

65

62

64

66

63

65

66

63

65

67

64

66

68

SHC

38

35

34

40

37

35

41

39

37

43

41

39

44

42

40

kW

5.0

5.0

5.0

5.0

5.0

5.0

5.0

5.0

5.0

5.0

5.0

5.0

5.0

5.0

5.0

75

TC

47

48

50

47

49

51

48

50

51

48

50

52

49

51

52

SHC

24

21

18

26

23

20

28

25

22

29

26

24

31

28

25

kW

5.4

5.4

5.4

5.4

5.4

5.4

5.4

5.4

5.4

5.4

5.4

5.4

5.4

5.4

5.4

85

TC

32

33

35

32

34

35

33

34

36

33

35

36

34

35

37

SHC

11

7

3

13

9

5

14

11

7

16

12

9

17

14

10

kW

5.9

5.9

5.9

5.9

5.9

5.9

5.9

5.9

5.9

5.9

5.9

5.9

5.9

5.9

5.9

95

TC

17

18

19

18

19

20

18

19

20

19

20

21

19

20

21

SHC

–3

–8

–12

–1

–6

–10

1

–4

–8

3

–2

–6

4

0

–4

kW

6.3

6.3

6.3

6.3

6.3

6.3

6.3

6.3

6.3

6.3

6.3

6.3

6.3

6.3

6.3

BF

Bypass Factor

Edb — Entering Dry-Bulb
Ewb — Entering Wet-Bulb
kW

Compressor Motor Power Input

ldb

Leaving Dry-Bulb

lwb

Leaving Wet-Bulb

SHC — Sensible Heat Capacity (1000 Btuh) Gross
TC

Total Capacity (1000 Btuh) Gross

t

ldb

= t

edb

sensible capacity (Btuh)

1.10 x cfm

h

lwb

= h

ewb

total capacity (Btuh)

4.5 x cfm

BYPASS
FACTOR

(BF)

ENTERING AIR DRY-BULB TEMP (F)

79

78

77

76

75

under 75

81

82

83

84

85

over 85

Correction Factor

.05

1.04

2.07

3.11

4.14

5.18

Use formula

shown below.

.10

.98

1.96

2.94

3.92

4.90

.20

.87

1.74

2.62

3.49

4.36

.30

.76

1.53

2.29

3.05

3.82

581

A155

-3

00