beautypg.com

Cooling capacities (cont) – Bryant 581A/B User Manual

Page 158

background image

158

PERFORMANCE DATA — 579F (cont)

COOLING CAPACITIES (cont)

LEGEND

NOTES:

1. Direct interpolation is permissible. Do not extrapolate.
2. The following formulas may be used:

Where: h

ewb

= Enthalpy of air entering evaporator coil

3. The SHC is based on 80 F edb temperature of air entering evaporator coil.

Below 80 F edb, subtract (corr factor x cfm) from SHC.
Above 80 F edb, add (corr factor x cfm) to SHC.

Interpolation is permissible.
Correction Factor = 1.10 x (1 – BF) x (edb – 80).

579F300 (25 Tons)

Temp (F)

Air Entering

Condenser

(Edb)

Evaporator Air Quantity — Cfm

7,000

8,000

Evaporator Air — Ewb (F)/BF

54/0.44

58/0.26

62/0.13

67/0.12

72/0.12

76/0.19

80/0.01

54/0.49

58/0.32

62/0.15

67/0.14

72/0.13

76/0.17

80/0.00

75

TC

256

270

298

325

349

370

266

268

280

304

324

352

379

SHC

243

229

198

164

133

106

266

251

246

209

168

137

107

kW

19.3

20.0

20.3

21.0

21.6

22.2

19.5

19.6

19.9

20.5

20.9

21.8

22.4

85

TC

249

251

265

289

315

340

361

260

262

272

294

321

344

367

SHC

249

238

226

194

160

130

103

260

254

243

205

167

135

104

kW

21.3

21.3

21.7

22.4

23.1

24.3

24.4

21.6

21.6

22.0

22.5

23.3

23.9

24.6

95

TC

244

245

257

279

306

328

349

254

256

262

284

310

332

355

SHC

244

230

223

190

156

127

99

254

249

238

201

163

131

100

kW

23.6

23.5

24.1

24.6

25.6

26.2

26.7

23.8

23.9

24.1

24.8

25.5

26.2

26.9

105

TC

237

238

247

269

293

315

336

246

247

253

274

298

319

343

SHC

237

233

218

185

152

122

95

246

245

233

197

159

127

96

kW

25.9

25.9

26.3

27.0

27.8

28.5

29.2

26.3

26.3

26.5

27.2

28.0

28.7

29.5

115

TC

229

231

237

258

283

302

322

238

239

243

264

286

306

328

SHC

229

225

213

181

148

119

91

238

239

228

193

155

123

91

kW

28.6

28.6

28.9

29.6

30.3

31.2

31.9

28.9

28.9

29.1

29.7

30.6

31.4

32.1

117

TC

228

230

236

256

279

299

237

237

241

260

283

304

SHC

228

225

212

180

147

118

237

237

227

192

154

122

kW

29.1

29.1

29.4

30.2

31.0

31.7

29.4

29.5

29.6

30.4

31.2

31.9

120

TC

226

226

232

252

276

234

234

238

257

280

SHC

226

225

211

179

145

234

234

225

190

152

kW

30.0

30.0

30.3

30.9

31.8

30.3

30.3

30.5

31.1

32.0

579F300 (25 Tons) (cont)

Temp (F)

Air Entering

Condenser

(Edb)

Evaporator Air Quantity — Cfm

9,000

10,000

Evaporator Air — Ewb (F)/BF

54/0.53

58/0.37

62/0.18

67/0.15

72/0.14

76/0.17

80/0.00

54/0.57

58/0.41

62/0.23

67/0.16

72/0.15

76/0.17

80/0.00

75

TC

277

276

286

310

336

361

385

286

284

291

314

341

365

390

SHC

277

269

261

221

178

142

108

286

284

274

232

186

147

108

kW

19.8

19.5

20.0

20.6

21.3

22.0

22.6

20.0

20.2

20.2

20.8

21.5

22.1

22.7

85

TC

271

272

277

300

326

349

373

278

278

282

304

330

354

378

SHC

271

264

257

217

175

139

104

278

278

269

228

182

143

105

kW

22.2

21.9

22.1

22.7

23.4

24.1

24.8

22.1

22.1

22.2

22.8

23.6

24.2

24.9

95

TC

263

263

268

289

316

337

360

270

270

273

293

319

341

364

SHC

263

263

251

213

171

135

100

270

270

262

223

177

139

101

kW

24.1

24.1

24.3

24.9

25.9

26.4

27.1

24.4

24.4

24.4

25.1

25.8

26.5

27.2

105

TC

255

255

258

278

302

326

346

261

262

264

282

306

328

352

SHC

255

255

246

208

166

132

96

261

262

254

219

173

135

97

kW

26.5

26.5

26.6

27.3

28.1

29.0

29.6

26.8

26.8

26.9

27.5

28.3

29.0

29.8

115

TC

247

246

249

267

290

311

253

253

255

270

293

315

SHC

247

246

239

204

162

127

253

253

245

214

168

131

kW

29.1

29.2

29.3

30.0

30.8

31.5

29.3

29.3

29.6

30.1

30.9

31.7

117

TC

244

244

247

265

288

308

251

251

253

268

291

SHC

244

244

237

203

161

126

251

251

243

213

168

kW

29.7

29.7

29.8

30.4

31.3

32.1

30.0

30.0

30.0

30.6

31.4

120

TC

241

242

244

261

248

248

250

264

SHC

241

242

235

201

248

248

239

212

kW

30.6

30.6

30.7

31.3

30.8

30.8

31.0

31.5

BF

Bypass Factor

Edb

Entering Dry-Bulb

Ewb

Entering Wet-Bulb

kW

Compressor Motor Power Input

ldb

Leaving Dry-Bulb

lwb

Leaving Wet-Bulb

SHC

Sensible Heat Capacity (1000 Btuh) Gross

TC

Total Capacity (1000 Btuh) Gross

t

ldb

=

t

edb

sensible capacity (Btuh)

1.10 x cfm

t

lwb

=

Wet-bulb temperature corresponding to enthalpy of air
leaving evaporator coil (h

lwb

)

h

lwb

=

h

ewb

total capacity (Btuh)

4.5 x cfm

BYPASS
FACTOR

(BF)

ENTERING AIR DRY-BULB TEMP (F)

79

78

77

76

75

under 75

81

82

83

84

85

over 85

Correction Factor

0.05

1.04

2.07

3.11

4.14

5.18

Use formula

shown below.

0.10

0.98

1.96

2.94

3.92

4.91

0.20

0.87

1.74

2.62

3.49

4.36

0.30

0.76

1.53

2.29

3.05

3.82

0.40

0.65

1.31

1.96

2.62

3.27

0.50

0.55

1.09

1.64

2.18

2.73

0.60

0.44

0.87

1.31

1.74

2.18

0.70

0.33

0.65

0.98

1.31

1.64

0TF

Q004

-0

12

5

7

9

F

18

0-

300