PERFORMANCE DATA (cont)

COOLING CAPACITIES, UNITS WITH HOT GAS REHEAT OPTION

LEGEND

NOTES:

1. Direct interpolation is permissible. Do not extrapolate.
2. The following formulas may be used:

t

lwb

= Wet-bulb temperature corresponding to enthalpy of air leaving evapo-

rator coil (h

lwb

)

Where: h

ewb

= Enthalpy of air entering evaporator coil

3. The SHC is based on 80 F edb temperature of air entering evaporator coil.

Below 80 F edb, subtract (corr factor x cfm) from SHC.
Above 80 F edb, add (corr factor x cfm) to SHC.

Interpolation is permissible.
Correction Factor = 1.10 x (1 – BF) x (edb – 80).

581A181 (15 TONS) UNIT WITH HOT GAS REHEAT IN COOLING MODE

Temp (F)

Air Entering

Condenser

(Edb)

Air Entering Evaporator — Cfm/BF

4500/0.02

5250/0.03

6000/0.04

6750/0.04

7500/0.05

Air Entering Evaporator — Ewb (F)

57

62

67

72

57

62

67

72

57

62

67

72

57

62

67

72

57

62

67

72

75

TC

166

179

193

214

175

186

202

221

183

191

208

227

190

195

212

232

197

199

216

236

SHC

165

152

129

108

175

166

140

115

183

178

150

121

190

189

159

127

197

196

168

133

kW

10.4

10.6

10.7

10.9

10.5

10.6

10.8

11.0

10.6

10.7

10.9

11.1

10.7

10.7

10.9

11.2

10.8

10.8

11.0

11.2

85

TC

162

174

189

209

171

180

195

216

179

185

200

222

186

189

205

226

192

194

208

230

SHC

162

150

127

106

171

163

137

113

179

175

147

119

186

185

156

125

192

192

164

131

kW

11.7

11.9

12.1

12.3

11.8

12.0

12.1

12.4

11.9

12.0

12.2

12.5

12.0

12.1

12.3

12.5

12.1

12.1

12.3

12.6

95

TC

158

169

182

202

166

174

187

209

174

179

194

214

181

183

198

218

187

188

201

221

SHC

158

148

126

104

166

160

134

110

174

172

145

116

181

180

154

122

187

187

163

128

kW

12.7

12.9

13.1

13.3

12.9

13.0

13.2

13.4

13.0

13.0

13.2

13.5

13.1

13.1

13.3

13.6

13.1

13.2

13.4

13.6

105

TC

153

163

178

195

162

168

181

201

169

172

188

206

175

177

191

209

181

181

194

213

SHC

153

145

123

101

162

157

133

107

169

167

142

113

175

175

151

119

181

181

160

125

kW

14.1

14.2

14.4

14.7

14.2

14.3

14.5

14.8

14.3

14.3

14.6

14.8

14.4

14.4

14.6

14.9

14.5

14.5

14.7

14.9

115

TC

148

156

171

188

157

161

176

193

163

165

180

197

169

170

183

201

174

175

185

203

SHC

148

141

120

98

157

153

130

104

163

162

139

110

169

169

148

116

174

174

156

122

kW

15.5

15.6

15.8

16.1

15.6

15.7

15.9

16.2

15.7

15.8

16.0

16.3

15.8

15.8

16.1

16.3

15.9

15.9

16.1

16.4

125

TC

143

149

163

179

151

153

168

184

157

158

171

188

163

163

174

190

167

167

176

192

SHC

143

138

117

95

151

149

126

101

157

156

136

107

163

163

144

112

167

167

153

118

kW

17.0

17.1

17.4

17.7

17.2

17.2

17.5

17.8

17.3

17.3

17.6

17.8

17.4

17.4

17.6

17.9

17.5

17.5

17.6

17.9

581A181 (15 TONS) UNIT WITH HOT GAS REHEAT — A IN REHEAT, B AND C OFF

Temp (F)

Air Entering

Condenser

(Edb)

Evaporator Air Quantity — Cfm/BF

4500/0.12

5250/0.14

6000/.015

6750/0.18

7500/0.18

Evaporator Air — Relative Humidity (%)

50

55

60

50

55

60

50

55

60

50

55

60

50

55

60

65

TC

55

57

59

56

58

59

56

58

60

57

59

60

57

59

61

SHC

34

32

30

36

34

32

37

35

33

38

36

35

40

38

36

kW

4.4

4.5

4.5

4.4

4.5

4.5

4.4

4.5

4.5

4.4

4.5

4.5

4.4

4.5

4.5

75

TC

42

44

45

43

44

46

43

45

46

43

45

46

44

45

47

SHC

22

19

17

23

21

18

25

22

20

26

24

21

28

25

23

kW

4.8

4.8

4.8

4.8

4.8

4.8

4.8

4.8

4.8

4.8

4.8

4.8

4.8

4.8

4.8

85

TC

29

30

31

29

31

32

30

31

32

30

32

33

31

32

33

SHC

9

6

3

11

8

5

13

10

7

14

11

8

16

12

9

kW

5.2

5.2

5.3

5.2

5.2

5.3

5.2

5.2

5.3

5.2

5.2

5.3

5.2

5.2

5.3

95

TC

15

16

17

16

17

18

16

18

18

17

18

19

17

18

19

SHC

–3

–7

–11

–1

–5

–9

1

–3

–7

2

–2

–5

4

0

–4

kW

5.6

5.6

5.6

5.6

5.6

5.6

5.6

5.6

5.6

5.6

5.6

5.6

5.6

5.6

5.6

581A181 (15 TONS) UNIT WITH HOT GAS REHEAT — A AND B IN REHEAT, C OFF

Temp (F)

Air Entering

Condenser

(Edb)

Evaporator Air Quantity — Cfm/BF

4500/0.12

5250/0.14

6000/.015

6750/0.18

7500/0.18

Evaporator Air — Relative Humidity (%)

50

55

60

50

55

60

50

55

60

50

55

60

50

55

60

65

TC

81

84

86

82

85

87

83

86

88

84

87

89

85

87

90

SHC

34

32

30

36

33

31

37

35

33

39

36

34

40

38

36

kW

7.8

7.9

7.9

7.8

7.9

7.9

7.8

7.9

7.9

7.8

7.9

7.9

7.8

7.9

7.9

75

TC

62

64

66

62

65

67

63

66

68

64

66

68

64

67

69

SHC

22

19

16

24

21

18

25

22

20

27

24

21

28

25

22

kW

8.5

8.5

8.5

8.5

8.5

8.5

8.5

8.5

8.5

8.5

8.5

8.5

8.5

8.5

8.5

85

TC

42

44

46

43

45

46

43

45

47

44

46

48

44

46

48

SHC

10

6

2

12

8

4

14

10

6

15

11

8

16

13

9

kW

9.2

9.2

9.3

9.2

9.2

9.3

9.2

9.2

9.3

9.2

9.2

9.3

9.2

9.2

9.3

95

TC

23

24

26

23

25

26

24

25

27

24

26

27

24

26

27

SHC

–2

–7

–11

0

–5

–9

2

–3

–7

3

–1

–6

5

0

–4

kW

9.9

9.9

9.9

9.9

9.9

9.9

9.9

9.9

9.9

9.9

9.9

9.9

9.9

9.9

9.9

BF

Bypass Factor

Edb — Entering Dry-Bulb
Ewb — Entering Wet-Bulb
kW

Compressor Motor Power Input

ldb

Leaving Dry-Bulb

lwb

Leaving Wet-Bulb

SHC — Sensible Heat Capacity (1000 Btuh) Gross
TC

Total Capacity (1000 Btuh) Gross

t

ldb

= t

edb

sensible capacity (Btuh)

1.10 x cfm

h

lwb

= h

ewb

total capacity (Btuh)

4.5 x cfm

BYPASS
FACTOR

(BF)

ENTERING AIR DRY-BULB TEMP (F)

79

78

77

76

75

under 75

81

82

83

84

85

over 85

Correction Factor

.05

1.04

2.07

3.11

4.14

5.18

Use for-

mula

shown
below.

.10

.98

1.96

2.94

3.92

4.90

.20

.87

1.74

2.62

3.49

4.36

.30

.76

1.53

2.29

3.05

3.82

5

81A1

55-

30
0