PERFORMANCE DATA (cont)
OUTDOOR SOUND POWER (TOTAL UNIT)
LEGEND
NOTE: The indoor sound power is available in Bryant’s Electronic Catalog
program (ECAT) for specific operating parameters.
EVAPORATOR-FAN MOTOR EFFICIENCY
*Single phase/3 phase.
NOTES:
1. Convert bhp to watts using the following formula:
2.
The EPACT (Energy Policy Act of 1992) regulates energy requirements
for specific types of indoor fan motors. Motors regulated by EPACT
include any general purpose, T-frame (three-digit, 143 and larger),
single-speed, foot mounted, polyphase, squirrel cage induction motors
of NEMA (National Electrical Manufacturers Association) design A and
B, manufactured for use in the United States. Ranging from 1 to 200
Hp, these continuous-duty motors operate on 230 and 460 volt, 60 Hz
power. If a motor does not fit into these specifications, the motor does
not have to be replaced by an EPACT-compliant energy-efficient motor.
Variable-speed motors are exempt from EPACT compliance require-
ments. Therefore, the indoor fan motors for Bryant 581B036-150 units
are exempt from these requirements.
ACCESSORY/FIOP ECONOMI$ER IV AND ECONOMI$ER2 STATIC PRESSURE* (in. wg) — 581B036-072
LEGEND
*The static pressure must be added to external static pressure. The sum and
the evaporator entering-air cfm should be used in conjunction with the Fan
Performance tables to determine indoor blower rpm and watts.
ACCESSORY/FIOP ECONOMI$ER IV AND ECONOMI$ER2 STATIC PRESSURE* (in. wg) — 581B090-150
LEGEND
*The static pressure must be added to external static pressure. The sum and
the evaporator entering-air cfm should be used in conjunction with the Fan
Performance tables to determine indoor blower rpm and watts.
UNIT
581B
SOUND
RATING
(dB)
OCTAVE BANDS
63
125
250
500
1000
2000
4000
8000
036,048
76
55.9
66.0
64.0
66.2
68.4
64.5
61.7
57.3
060,072
80
59.1
68.9
68.7
71.9
74.0
68.9
65.7
59.0
090,102
82
62.2
69.3
71.5
74.7
76.2
72.9
68.7
61.5
120
84
64.6
71.1
73.3
76.9
77.6
73.7
70.6
63.7
150
86
63.7
69.9
72.5
78.2
81.1
77.3
73.3
66.8
dB
—
Sound Levels (decibels)
UNIT SIZE 581B
EFFICIENCY%
036,048
75
060
74/84*
072
84
090,102
80
120
85
150
87
watts =
bhp (746)
motor efficiency
COMPONENT
CFM
1250
1500
1750
2000
2250
2500
2750
3000
Vertical EconoMi$er IV and EconoMi$er2
0.045
0.065
0.08
0.12
0.145
0.175
0.22
0.255
Horizontal EconoMi$er IV and EconoMi$er2
—
—
0.1
0.125
0.15
0.18
0.225
0.275
FIOP — Factory-Installed Option
COMPONENT
CFM
2250
2500
2750
3000
3250
3500
3750
4000
4250
4500
4750
5000
5250
6250
Vertical EconoMi$er IV and
EconoMi$er2
0.06
0.075
0.09
0.115
0.13
0.15
0.17
0.195
0.22
0.25
0.285
0.325
0.36
—
Horizontal EconoMi$er IV and
EconoMi$er2
—
0.1
0.125
0.15
0.18
0.21
0.25
0.275
0.3
0.34
0.388
—
—
—
FIOP — Factory-Installed Option
581
B0
36
-15
0