Bryant 580J***(D User Manual
Submittal data, 580j***(d,f), Description
580J***(D,F)
SINGLE PACKAGE ROOFTOP
GAS HEATING/ELECTRIC COOLING UNIT
TWO STAGE COOLING CAPACITY CONTROL WITH NOVATIONt COIL
SIZES 08, 12, 14 WITH PURONR (R--410A) REFRIGERANT
Submittal Data
®
This product has been designed and manufactured
to meet Energy Star® criteria for energy efficiency.
However, proper refrigerant charge and proper air
flow are critical to achieve rated capacity and effi-
ciency. Installation of this product should follow all
manufacturer’s refrigerant charging and air flow in-
structions.
Failure to confirm proper charge and
air flow may reduce energy efficiency and short-
en equipment life.
DESCRIPTION
580J***(D,F) units are high--efficiency, single--packaged
electric cooling, gas heating units that are pre--wired and
pre--charged with PuronR (R--410A) HFC refrigerant.
Units utilize an all aluminum flat micro--channel tube
with louvered fins condenser coil—NOVATIONt. The
units are factory tested in both heating and cooling modes.
These units meet the ASHRAE 90.1--2007 and Energy
Star minimum efficiency levels as well as also meeting
2010 efficiency standards.
STANDARD FEATURES
Base Unit
S
Puron (R--410A) HFC refrigerant
S
ARI certified efficiency levels up to 11.1 EER
S
Rated in accordance with ARI Standard 360
S
Designed in accordance with Underwriters’ Laboratories Std
1995 and listed by UL and UL, Canada
S
Two--stage cooling capacity control
S
Non--corrosive composite sloping design; side or center drain
condensate pan. Meets ASHRAE Standard 62
S
Standard cooling operating range from 40_F up to 115_F
(4_C up to 46_C). Field installable accessory extends the
minimum down to --20_F (--29_C).
S
Convertible from vertical to horizontal airflow for slab mounting
S
Two--inch disposable return air filters
S
Thru--the--bottom power and gas entry capability
S
Single point gas and electric connections
S
24--volt control circuit protected with resettable circuit breaker
and 75--VA transformer
S
Belt drive, constant torque, permanently lubricated
evaporator–fan motor
S
Totally enclosed condenser motors with permanently lubricated
bearings
S
Low--pressure and high--pressure switches
S
Full perimeter base rail with built--in rigging adapters and fork
truck slots
S
Centralized Terminal Board for component and unit wiring
connections
Cabinet
S
Access panels with easy grip handles and NO--STRIP screw
collar
S
Pre--painted exterior panels and primer--coated interior panels
tested to 500 hours salt spray protection
S
Fully insulated cabinet
S
Tool--less filter access door
Refrigerant System
S
Acutrolt refrigerant metering system
S
Liquid line filter drier
S
Scroll compressors with internal line--break overload protection
S
Copper
tube
, aluminum fin evaporator coil
S
NOVATION all aluminum condenser coil
S
Removable gauge line plugs for reading refrigerant pressure
with unit panels in place
Gas Heat
S
IGC solid--state gas heat exchanger control for on--board
diagnostics, anti--cycle protection, LED error code designation,
burner control logic and energy saving indoor fan motor delay
S
Gas efficiencies up to 82%
S
Designed in accordance with ANSI Z21.47 (design and test
standard for gas furnaces) and ANSI Z233.1 (National Fuel Gas
code relating to appliance installation requirements)
S
Induced draft combustion
S
Redundant gas valve, with up to 2 stages of heating
S
Flame roll--out safety protector
S
Solid--state electronic direct spark ignition system