PERFORMANCE DATA (cont)

COOLING CAPACITIES, UNITS WITH HOT GAS REHEAT OPTION (cont)

LEGEND

NOTES:

1. Direct interpolation is permissible. Do not extrapolate.
2. The following formulas may be used:

t

lwb

= Wet-bulb temperature corresponding to enthalpy of air leaving evapo-

rator coil (h

lwb

)

Where: h

ewb

= Enthalpy of air entering evaporator coil

3. The SHC is based on 80 F edb temperature of air entering evaporator coil.

Below 80 F edb, subtract (corr factor x cfm) from SHC.
Above 80 F edb, add (corr factor x cfm) to SHC.

Interpolation is permissible.
Correction Factor = 1.10 x (1 – BF) x (edb – 80).

581A300 (25 TONS) UNIT WITH HOT GAS REHEAT IN COOLING MODE

Temp (F)

Air Entering

Condenser

(Edb)

Air Entering Evaporator — Cfm/BF

7000/0.042

8250/0.052

9500/0.062

10,750/0.072

12,000/0.082

Air Entering Evaporator — Ewb (F)

57

62

67

72

57

62

67

72

57

62

67

72

57

62

67

72

57

62

67

72

75

TC

245

268

293

318

259

282

303

333

274

291

314

340

289

301

322

348

305

309

332

356

SHC

245

229

197

162

259

254

213

173

274

271

230

183

289

287

247

195

305

298

267

203

kW

16.4

17.0

17.6

18.2

16.7

17.4

17.9

18.6

17.1

17.6

18.2

18.8

17.5

17.8

18.4

19.0

18.0

18.1

18.6

19.2

85

TC

233

259

278

309

256

273

293

324

271

282

305

330

285

290

312

337

298

303

321

343

SHC

233

228

186

158

256

252

211

171

271

264

229

180

285

276

246

191

298

295

261

201

kW

17.9

18.7

19.3

19.9

18.5

19.1

19.7

20.4

19.0

19.4

20.0

20.8

19.3

19.6

20.2

21.1

19.8

19.9

20.4

21.3

95

TC

230

252

276

303

251

265

284

314

269

274

290

326

274

282

300

332

283

293

308

334

SHC

230

225

191

156

251

249

202

166

269

269

220

181

274

274

238

190

283

280

259

197

kW

20.0

20.8

21.4

22.1

20.7

21.2

21.5

22.4

21.3

21.4

21.9

23.0

21.5

21.7

22.1

23.2

21.6

22.0

22.5

23.3

105

TC

226

245

268

292

242

253

277

301

255

264

284

308

266

275

290

314

278

281

294

319

SHC

226

223

188

153

242

241

205

163

255

255

221

171

265

265

240

185

278

278

253

194

kW

22.0

22.8

23.3

24.3

22.7

23.1

23.7

24.7

23.1

23.4

24.0

25.0

23.6

23.7

24.3

25.2

24.0

24.1

24.4

25.4

115

TC

221

233

258

281

232

242

267

290

247

253

274

297

253

260

275

302

267

269

279

306

SHC

221

217

183

149

232

230

200

160

247

246

217

170

253

254

233

179

267

267

248

189

kW

24.3

25.1

25.7

26.7

24.8

25.4

26.1

27.1

25.3

25.8

26.4

27.2

25.8

26.0

26.5

27.3

26.1

26.3

26.7

27.4

125

TC

216

223

247

268

225

230

253

275

237

240

256

280

247

248

260

285

254

255

263

288

SHC

216

212

181

145

225

223

196

155

237

236

211

163

247

247

228

174

254

254

242

184

kW

26.9

27.1

28.0

29.0

27.4

27.5

28.3

29.4

27.8

27.9

28.5

29.6

28.2

28.3

28.7

29.8

28.5

28.6

28.9

29.9

581A300 (25 TONS) UNIT WITH HOT GAS REHEAT — A IN REHEAT, B OFF

Temp (F)

Air Entering

Condenser

(Edb)

Evaporator Air Quantity — Cfm/BF

7500/0.045

8250/0.055

9500/0.065

10,750/0.075

12,000/0.085

Evaporator Air — Relative Humidity (%)

50

55

60

50

55

60

50

55

60

50

55

60

50

55

60

65

TC

79

83

87

80

84

88

81

85

89

82

86

90

83

87

91

SHC

39

33

28

41

35

30

43

37

32

45

39

34

47

41

36

kW

11

11

11

11

11

11

11

11

11

11

11

11

11

11

11

75

TC

56

61

65

57

62

66

59

63

67

60

64

68

61

65

69

SHC

18

11

5

20

12

6

22

15

8

24

16

10

26

18

12

kW

11

11

11

11

11

11

11

11

11

11

11

11

11

11

11

85

TC

34

38

42

35

39

43

37

41

45

38

42

46

39

43

47

SHC

–2

–11

–19

–1

–10

–18

1

–8

–16

3

–7

–14

4

–5

–13

kW

11

11

12

11

12

12

12

12

12

12

12

12

12

12

12

95

TC

12

16

19

13

17

21

15

19

22

16

20

24

17

22

25

SHC

–23

–33

–42

–22

–32

–41

–20

–31

–40

–19

–30

–39

–17

–28

–38

kW

12

12

12

12

12

12

12

12

12

12

12

12

12

12

12

581A300 (25 TONS) UNIT WITH HOT GAS REHEAT — A IN REHEAT, B ON

Temp (F)

Air Entering

Condenser

(Edb)

Evaporator Air Quantity — Cfm/BF

7500/0.045

8250/0.055

9500/0.065

10,750/0.075

12,000/0.085

Evaporator Air — Relative Humidity (%)

50

55

60

50

55

60

50

55

60

50

55

60

50

55

60

65

TC

211

222

231

215

226

235

220

232

241

226

237

247

230

242

252

SHC

123

115

109

129

121

115

139

131

124

147

139

133

155

147

140

kW

19

19

20

19

19

20

19

19

20

19

20

20

19

20

20

75

TC

182

193

202

185

196

205

189

200

210

192

204

214

196

208

218

SHC

103

93

85

110

100

91

120

110

101

128

118

110

136

126

118

kW

20

21

21

20

21

21

21

21

21

21

21

21

21

21

21

85

TC

153

164

174

155

166

176

157

169

178

159

171

181

161

173

184

SHC

84

72

62

90

78

68

100

88

78

110

97

87

118

106

95

kW

22

22

22

22

22

22

22

22

22

22

22

22

22

22

22

95

TC

124

135

145

125

136

146

125

137

147

126

138

148

127

139

149

SHC

64

50

38

71

57

45

81

67

55

91

76

64

99

85

72

kW

23

23

23

23

23

23

23

23

24

23

23

24

23

24

24

BF

Bypass Factor

Edb — Entering Dry-Bulb
Ewb — Entering Wet-Bulb
kW

Compressor Motor Power Input

ldb

Leaving Dry-Bulb

lwb

Leaving Wet-Bulb

SHC — Sensible Heat Capacity (1000 Btuh) Gross
TC

Total Capacity (1000 Btuh) Gross

t

ldb

= t

edb

sensible capacity (Btuh)

1.10 x cfm

h

lwb

= h

ewb

total capacity (Btuh)

4.5 x cfm

BYPASS
FACTOR

(BF)

ENTERING AIR DRY-BULB TEMP (F)

79

78

77

76

75

under 75

81

82

83

84

85

over 85

Correction Factor

.05

1.04

2.07

3.11

4.14

5.18

Use formula

shown below.

.10

.98

1.96

2.94

3.92

4.90

.20

.87

1.74

2.62

3.49

4.36

.30

.76

1.53

2.29

3.05

3.82

5

81A1

55-

30
0