580f180-300 – Bryant 581A/B User Manual
Page 13
13
ARI* CAPACITY RATINGS — 580F180-300
LEGEND
*Air Conditioning and Refrigeration Institute.
NOTES:
1. Rated in accordance with ARI Standards 360 and 270.
2. ARI ratings are net values, reflecting the effects of circulating fan
heat.
3. Ratings are based on:
Cooling Standard: 80 F db, 67 F wb indoor entering-air tempera-
ture and 95 F db air entering outdoor unit.
IPLV Standard: 80 F db, 67 F wb indoor entering-air temperature
and 80 F db outdoor entering-air temperature.
4. All 580F180-300 units are in compliance with ASHRAE 90.1-
1999 Energy Standard for minimum SEER and EER require-
ments. Refer to state and local codes or visit the following website:
http://solstice.crest.org/efficiency/bcap to determine if compliance
with this standard pertains to a given geographical area of the
United States.
HEATING CAPACITIES AND EFFICIENCIES — 580F180-300
*All units are 2-stage heat.
NOTE: Minimum allowable temperature of mixed-air entering the heat exchanger during first-stage
heating is 45 F. There is no minimum mixed-air temperature limitation during second-stage heating.
For entering-air temperatures below 45 F both stages of heat must be energized together to minimize
condensation issues and ensure proper unit operation.
AIR QUANTITY LIMITS (Cooling)
COOLING OPERATION
LOW OUTDOOR TEMPERATURE OPERATING LIMITS (F)
UNIT SIZE
580F
(Low Heat)
NOMINAL
TONS
NET COOLING
CAPACITY (Btuh)
TOTAL
WATTS
EER
SOUND
RATING
(dB)
IPLV
180
15
176,000
17,064
9.5
88
9.5
210
18
202,000
21,166
9.7
88
10.2
240
20
236,000
24,832
9.5
94
10.1
300
25
278,000
28,535
9.7
94
10.4
UNIT SIZE
580F
(High Heat)
NOMINAL
TONS
NET COOLING
CAPACITY (Btuh)
TOTAL
WATTS
EER
SOUND
RATING
(dB)
IPLV
180
15
176,000
17,179
9.5
88
9.5
210
18
202,000
21,301
9.7
88
10.1
240
20
236,000
24,832
9.5
94
10.0
300
25
277,000
29,067
9.5
94
10.0
Bels — Sound Levels (1 bel = 10 decibels)
db
— Dry Bulb
EER — Energy Efficiency Ratio
IPLV — Integrated Part-Load Values
wb
— Wet Bulb
UNIT
580F
HEATING INPUT
(Btuh)
Stage 2/Stage 1*
OUTPUT CAPACITY
(Btuh)
TEMPERATURE
RISE (F)
STEADY-STATE
EFFICIENCY (%)
MINIMUM
HEATING CFM
180275
275,000/206,000
223,000
15-45
81.0
3750
180360
360,000/270,000
292,000
20-50
81.0
3830
210275
275,000/206,000
223,000
15-45
81.0
4580
210360
360,000/270,000
292,000
20-50
81.0
5400
240275
275,000/206,000
223,000
15-45
81.0
4580
240360
360,000/270,000
292,000
20-50
81.0
5400
300275
275,000/206,000
223,000
15-45
81.0
4580
300360
360,000/270,000
292,000
20-50
81.0
5400
UNIT 580F
MINIMUM CFM
MAXIMUM CFM
180
4500
7,500
210
5400
9,000
240
6000
10,000
300
7000
11,250
UNITS
TEMPERATURE
All — Standard Unit
40
180 and 210 with Low Ambient Kit
10
240 and 300 with Low Ambient Kit
25
All with Motormaster® Head Pressure Control
–20