PERFORMANCE DATA — 579F (cont)

COOLING CAPACITIES (cont)

LEGEND

NOTES:

1. Direct interpolation is permissible. Do not extrapolate.
2. The following formulas may be used:

Where: h

ewb

= Enthalpy of air entering evaporator coil

3. The SHC is based on 80 F edb temperature of air entering evaporator coil.

Below 80 F edb, subtract (corr factor x cfm) from SHC.
Above 80 F edb, add (corr factor x cfm) to SHC.

Interpolation is permissible.
Correction Factor = 1.10 x (1 – BF) x (edb – 80).

579F180 (15 Tons) (cont)

Temp (F)

Air Entering

Condenser

(Edb)

Evaporator Air Quantity — Cfm

7500

Evaporator Air — Ewb (F)/BF

54/0.65

58/0.52

62/0.41

67/0.30

72/0.28

76/0.27

80/0.03

75

TC

188

183

193

206

223

239

256

SHC

188

183

170

148

120

95

70

kW

12.9

12.8

13.0

13.2

13.6

13.9

14.2

85

TC

183

183

187

199

215

233

249

SHC

183

183

167

145

117

94

68

kW

14.4

14.4

14.4

14.7

15.1

15.9

16.3

95

TC

177

177

181

191

207

222

237

SHC

177

177

161

142

114

90

65

kW

15.9

15.9

16.0

16.3

16.7

17.0

17.3

105

TC

171

171

175

183

199

213

228

SHC

171

171

154

138

111

87

62

kW

17.6

17.6

17.7

18.0

18.4

18.7

19.0

115

TC

164

164

169

175

190

203

217

SHC

164

164

146

135

108

84

59

kW

19.4

19.4

19.5

19.7

20.2

20.5

20.9

117

TC

163

163

167

173

188

201

SHC

163

163

145

134

107

84

kW

19.7

19.7

19.9

20.0

20.5

20.9

120

TC

161

161

165

170

SHC

161

161

143

133

kW

20.2

20.3

20.4

20.6

BF

Bypass Factor

Edb

Entering Dry-Bulb

Ewb

Entering Wet-Bulb

kW

Compressor Motor Power Input

ldb

Leaving Dry-Bulb

lwb

Leaving Wet-Bulb

SHC

Sensible Heat Capacity (1000 Btuh) Gross

TC

Total Capacity (1000 Btuh) Gross

t

ldb

=

t

edb

sensible capacity (Btuh)

1.10 x cfm

t

lwb

=

Wet-bulb temperature corresponding to enthalpy of air
leaving evaporator coil (h

lwb

)

h

lwb

=

h

ewb

total capacity (Btuh)

4.5 x cfm

BYPASS
FACTOR

(BF)

ENTERING AIR DRY-BULB TEMP (F)

79

78

77

76

75

under 75

81

82

83

84

85

over 85

Correction Factor

0.05

1.04

2.07

3.11

4.14

5.18

Use formula

shown below.

0.10

0.98

1.96

2.94

3.92

4.91

0.20

0.87

1.74

2.62

3.49

4.36

0.30

0.76

1.53

2.29

3.05

3.82

0.40

0.65

1.31

1.96

2.62

3.27

0.50

0.55

1.09

1.64

2.18

2.73

0.60

0.44

0.87

1.31

1.74

2.18

0.70

0.33

0.65

0.98

1.31

1.64

0TF

Q004

-0
12

579

F18

0

-300