beautypg.com

Cooling capacities (cont) – Bryant 581A/B User Manual

Page 154

background image

154

PERFORMANCE DATA — 579F (cont)

COOLING CAPACITIES (cont)

LEGEND

NOTES:

1. Direct interpolation is permissible. Do not extrapolate.
2. The following formulas may be used:

Where: h

ewb

= Enthalpy of air entering evaporator coil

3. The SHC is based on 80 F edb temperature of air entering evaporator coil.

Below 80 F edb, subtract (corr factor x cfm) from SHC.
Above 80 F edb, add (corr factor x cfm) to SHC.

Interpolation is permissible.
Correction Factor = 1.10 x (1 – BF) x (edb – 80).

579F216 (18 Tons)

Temp (F)

Air Entering

Condenser

(Edb)

Evaporator Air Quantity — Cfm

5400

6000

Evaporator Air — Ewb (F)/BF

54/0.49

58/0.31

62/0.20

67/0.18

72/0.16

76/0.19

80/0.05

54/0.53

58/0.35

62/0.23

67/0.19

72/0.17

76/0.19

80/0.05

75

TC

194

198

206

223

243

260

277

200

203

210

227

246

263

SHC

194

178

169

146

121

99

79

200

191

177

152

125

102

kW

13.6

13.7

13.9

14.2

14.6

15.0

15.2

13.7

13.8

14.0

14.4

14.7

15.1

85

TC

189

192

200

217

235

252

269

195

195

204

220

239

255

SHC

189

176

166

143

118

97

76

195

195

174

149

123

100

kW

15.1

15.2

15.4

15.9

16.3

16.6

16.9

15.3

15.3

15.7

16.0

16.4

16.8

95

TC

183

184

193

209

227

243

189

190

196

212

230

246

SHC

183

181

162

140

115

94

189

190

170

146

120

97

kW

16.8

16.8

17.1

17.6

18.0

18.4

17.0

17.0

17.2

17.6

18.1

18.5

105

TC

177

178

185

201

218

234

183

185

189

204

221

237

SHC

177

178

159

137

112

91

183

185

166

143

116

94

kW

18.6

18.6

18.8

19.3

19.8

20.2

18.8

18.6

18.9

19.4

19.9

20.3

115

TC

171

171

177

192

209

224

176

177

181

195

212

226

SHC

171

171

154

133

109

88

176

177

161

139

113

90

kW

20.5

20.5

20.7

21.2

21.8

22.1

20.7

20.7

20.8

21.3

21.8

22.2

117

TC

170

170

176

191

207

222

175

175

180

193

210

224

SHC

170

170

154

132

108

87

175

175

160

138

112

90

kW

20.9

20.9

21.1

21.6

22.1

22.5

21.1

21.1

21.2

21.7

22.2

22.6

120

TC

168

168

173

188

204

173

173

177

191

207

SHC

168

168

152

131

107

173

173

159

137

111

kW

21.5

21.5

21.7

22.2

22.7

21.7

21.7

21.8

22.3

22.8

579F216 (18 Tons) (cont)

Temp (F)

Air Entering

Condenser

(Edb)

Evaporator Air Quantity — Cfm

7000

8000

Evaporator Air — Ewb (F)/BF

54/0.58

58/0.42

62/0.29

67/0.21

72/0.20

76/0.20

80/0.05

54/0.62

58/0.48

62/0.36

67/0.23

72/0.22

76/0.21

80/0.04

75

TC

209

209

215

232

251

268

216

217

221

236

255

272

SHC

209

209

189

162

132

106

216

217

198

171

138

109

kW

13.9

13.9

14.1

14.5

14.9

15.2

14.1

14.1

14.2

14.5

15.0

15.3

85

TC

203

204

209

224

243

260

211

211

215

228

247

263

SHC

203

204

185

159

129

103

211

211

192

168

135

107

kW

15.5

15.5

15.7

16.1

16.5

16.9

15.7

15.7

15.8

16.2

16.6

17.0

95

TC

197

197

202

216

235

251

204

204

209

220

238

254

SHC

197

197

180

156

126

100

204

204

185

165

132

104

kW

17.2

17.2

17.4

17.8

18.2

18.7

17.4

17.4

17.6

17.9

18.3

18.7

105

TC

191

191

195

208

225

241

197

197

202

211

228

244

SHC

191

191

175

152

123

97

197

197

177

161

128

100

kW

19.0

19.0

19.2

19.5

20.0

20.5

19.2

19.2

19.3

19.6

20.1

20.6

115

TC

184

184

188

199

215

230

190

190

194

202

218

SHC

184

184

168

149

119

94

190

190

170

158

125

kW

21.0

21.0

21.1

21.5

22.0

22.4

21.1

21.1

21.2

21.6

22.1

117

TC

183

183

187

197

214

228

188

188

192

200

216

SHC

183

183

166

148

118

93

188

188

171

157

124

kW

21.3

21.4

21.5

21.8

22.4

22.7

21.5

21.5

21.7

22.0

22.5

120

TC

180

180

185

194

210

186

186

190

197

SHC

180

180

163

147

117

186

186

172

156

kW

21.9

22.0

22.1

22.4

23.0

22.1

22.1

22.2

22.5

BF

Bypass Factor

Edb

Entering Dry-Bulb

Ewb

Entering Wet-Bulb

kW

Compressor Motor Power Input

ldb

Leaving Dry-Bulb

lwb

Leaving Wet-Bulb

SHC

Sensible Heat Capacity (1000 Btuh) Gross

TC

Total Capacity (1000 Btuh) Gross

t

ldb

=

t

edb

sensible capacity (Btuh)

1.10 x cfm

t

lwb

=

Wet-bulb temperature corresponding to enthalpy of air
leaving evaporator coil (h

lwb

)

h

lwb

=

h

ewb

total capacity (Btuh)

4.5 x cfm

BYPASS
FACTOR

(BF)

ENTERING AIR DRY-BULB TEMP (F)

79

78

77

76

75

under 75

81

82

83

84

85

over 85

Correction Factor

0.05

1.04

2.07

3.11

4.14

5.18

Use formula

shown below.

0.10

0.98

1.96

2.94

3.92

4.91

0.20

0.87

1.74

2.62

3.49

4.36

0.30

0.76

1.53

2.29

3.05

3.82

0.40

0.65

1.31

1.96

2.62

3.27

0.50

0.55

1.09

1.64

2.18

2.73

0.60

0.44

0.87

1.31

1.74

2.18

0.70

0.33

0.65

0.98

1.31

1.64

0TF

Q004

-0

12

5

7

9

F

18

0-

300