PERFORMANCE DATA — 579F (cont)

COOLING CAPACITIES (cont)

LEGEND

NOTES:

1. Direct interpolation is permissible. Do not extrapolate.
2. The following formulas may be used:

Where: h

ewb

= Enthalpy of air entering evaporator coil

3. The SHC is based on 80 F edb temperature of air entering evaporator coil.

Below 80 F edb, subtract (corr factor x cfm) from SHC.
Above 80 F edb, add (corr factor x cfm) to SHC.

Interpolation is permissible.
Correction Factor = 1.10 x (1 – BF) x (edb – 80).

579F240 (20 Tons) (cont)

Temp (F)

Air Entering

Condenser

(Edb)

Evaporator Air Quantity — Cfm

10,000

Evaporator Air — Ewb (F)/BF

54/0.65

58/0.52

62/0.40

67/0.26

72/0.24

76/0.24

80/0.04

75

TC

250

250

256

267

294

314

SHC

250

250

227

200

161

127

kW

15.8

15.8

15.9

16.1

16.7

17.1

85

TC

243

244

249

262

284

303

SHC

243

244

220

198

158

124

kW

17.6

17.8

17.7

18.0

18.5

18.9

95

TC

236

236

241

252

274

292

SHC

236

236

212

194

154

121

kW

19.5

19.5

19.7

19.9

20.4

20.9

105

TC

228

228

234

242

263

281

SHC

228

228

203

190

151

117

kW

21.6

21.6

21.8

22.0

22.5

22.9

115

TC

220

220

223

232

251

268

SHC

220

220

207

186

147

113

kW

23.9

23.9

23.9

24.2

24.7

25.2

117

TC

218

218

221

230

249

266

SHC

218

218

205

185

146

112

kW

24.3

24.3

24.4

24.7

25.2

25.6

120

TC

215

215

218

226

245

SHC

215

215

203

183

145

kW

25.1

25.1

25.1

25.4

25.9

BF

Bypass Factor

Edb

Entering Dry-Bulb

Ewb

Entering Wet-Bulb

kW

Compressor Motor Power Input

ldb

Leaving Dry-Bulb

lwb

Leaving Wet-Bulb

SHC

Sensible Heat Capacity (1000 Btuh) Gross

TC

Total Capacity (1000 Btuh) Gross

t

ldb

=

t

edb

sensible capacity (Btuh)

1.10 x cfm

t

lwb

=

Wet-bulb temperature corresponding to enthalpy of air
leaving evaporator coil (h

lwb

)

h

lwb

=

h

ewb

total capacity (Btuh)

4.5 x cfm

BYPASS
FACTOR

(BF)

ENTERING AIR DRY-BULB TEMP (F)

79

78

77

76

75

under 75

81

82

83

84

85

over 85

Correction Factor

0.05

1.04

2.07

3.11

4.14

5.18

Use formula

shown below.

0.10

0.98

1.96

2.94

3.92

4.91

0.20

0.87

1.74

2.62

3.49

4.36

0.30

0.76

1.53

2.29

3.05

3.82

0.40

0.65

1.31

1.96

2.62

3.27

0.50

0.55

1.09

1.64

2.18

2.73

0.60

0.44

0.87

1.31

1.74

2.18

0.70

0.33

0.65

0.98

1.31

1.64

0TF

Q004

-0
12

579

F18

0

-300