FLUE INSTALLATION

INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR 24 i junior/28 i junior
8 716 107 336b (11/05)

24

IN

ST

AL

LA

TI

O

N

FLUE INSTALLATION

MEASURING THE FLUE (Extension Flue Kits):
ONLY CUT EXTENDED FLUE LENGTHS

As with the Standard Flue measure from the
outside wall to the centre line of the flue
turret.
Subtract the length of the Standard Flue
and turret (725mm) from length L .
Subtract the full length 1m extension(s)
from the figure.
Cut one of the 1m extensions to the remainder.
Cut both tubes square taking care not to distort
the tubes.
Remove any burrs.

EXAMPLE:

Length L = 2380mm

Subtract Standard Flue+Turret — 686mm

Subtract Full Extension — 960mm

Cut Length = 734mm

NOTE: The minimum length a flue extension

can be cut to is 100mm

NOTE: Where extensions are reduced, cut
length which DOES NOT contain the seal.

ADDITION OF FLUE BENDS:

When flue bends are being used an allowance

of 98mm per bend must be allowed from the

centre line of the bend. In the example shown

using a flue extension with 2 bends will

achieve a total length of 1148mm.

Clamp

Clamp

Extension

734mm

Cut Length

Standard Flue

Seal

2380mm

Required Length

94mm

94mm