CONDENSATE PIPEWORK

CONDENSATE PIPEWORK:
• The condensate pipe must be a minimum of

22mmØ plastic pipe.

• The condensate pipework must fall at

least 50mm per metre towards the outlet
and should take the shortest practicable
route.

• The pipework must follow one of the options

shown opposite into an internal serviceable
trap (min. 75mm) such as a sink/washing
machine) or discharge direct into a vent
stack (E) 450mm min. above pipe invert or
into a gulley (D) below ground but above the
water level.

• Use waterproof pipe insulation in exposed

positions and for external pipework.

1 Internal sink/washing machine drain

2 Internal waste drainage system

3 Soil/vent stack

4 External drainage system

5 External condensate absorption point

A - Condensate from boiler

B - Sink

C - 22mmØ plastic condensate pipe

D - Gulley

E - Internal soil and vent stack

F - Serviceable waste trap (75mm min)

G - 300mm x 100mmØ sealed plastic tube

H - Ground level

J - Drainage holes 50mm from base of tube

(12mmØ at 25mm centres) facing away from

building

K - Limestone chippings

I M P ORTANT: Ensure t here are no
blockages in the pipe run.

CONDENSATE PIPEWORK