BOILER LOCATION & CLEARANCES

INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR 24 i junior/28 i junior

8 716 107 336b (11/05)

13

P

R

E -

IN

ST

AL

LA

TI

O

N

BOILER LOCATION &

CLEARANCES

This boiler is only suitable for installing internally
within a property at a suitable location onto a
fixed, rigid non-combustible surface at least the
same size as the boiler and capable of support-
ing the boiler weight.

COMPARTMENTS:
Follow the requirements of B S6798 and
BS5440 Part 2 and note:
• Minimum clearances must be maintained
• An access door is required to install, service

and maintain the boiler and any ancilliary
equipment.

• If fitting the boiler into an airing cupboard

use a non-combustible perforated material
(maximum hole sizes of 13mm) to separate
the boiler from the airing space.

BOILER CLEARANCES:
The diagram opposite shows the minimum
space required to install and service the boiler.

If a boiler is installed in a compartment with
clearances less than shown in the tables oppo-
site, ventilation is required. Refer to tables
below for ventilation requirements.

BOILER CLEARANCES - UNVENTILATED
COMPARTMENTS:
The tables opposite show the options for the
minimum space required to install and service
the boiler inside an unventilated compartment.

24 & 28 kW

Vent

To room or

Direct to

position

internal space

outside

High

Minimum free

Minimum

level

area 122 cm

2

free area
61 cm

2

Low

Minimum free

Minimum

level

area 122 cm

2

free area
61cm

2

SERVICING CLEARANCES
VENTED COMPARTMENT

VENTILATION FREE COMPARTMENTS
INSTALLATION CLEARANCES

Using 100mm flue kit

1080mm

Using 125mm flue kit

- 1110mm

Ventilation Free Compartments Installation Clearances

The suggested total unventilated compartment minimum clearances are:

Side

Above

Below

Front (to removable door)

400mm

170mm approx.

200mm

100mm

(30mm above

the elbow)

(Note: Top and bottom clearances must not be reduced below these values as they are the
minimum required for servicing).

If Side Clearances are Reduced

350mm 441mm

129mm

300mm

523mm

161mm

250mm

617mm

200mm

200mm

727mm

243mm

150mm

856mm

295mm

100mm

1012mm

358mm

50mm

1202mm

434mm

If total side clearance is
reduced to:

Then overall height clearances
must be increased to (approx):

OR

Front clearance (to removable
door) must be increased to:

If Front Clearance is Reduced

50mm 511mm

505mm

25mm

596mm

569mm

If front clearance (to
removable door) is
reduced to:

Then overall height clearances
must be increased to (approx):

OR

Total side clearance must be
increased to: