10.2.5 Submenu 'Parameter' - Output
Damping:
An average value of the pressure values applied to the sensor is calculated over the
predefined integration time. The following integration times can be set:
• 0, 1, 5, 20 and 40 s.
Output inversion:
The output signal can be inverted or not inverted.
• inverted
20 ... 4 mA
• not inverted 4 ... 20 mA
Alarm/Error:
Here the current value is displayed, which is set for an error message:
• 21.0 mA (upscale) or
• 36 mA (downscale).
Output current limits:
Here the range of output current is set.
• 3.8 ... 20.5 mA
When the applied pressure rises beyond the nominal range the current value ends
at the set limit value.
• 4 ... 20 mA
When the applied pressure rises beyond the nominal range and the alarm goes off
a reset must be carried out, or the power supply must be cut
(see also chapter 10.2.7).